CONTROL SET POINT AND CONFIGURATION LOG
Model Number: _____________________________
Serial Number: ______________________________
Date: ______________________________________
Technician: _________________________________
Software Versions: ___________________________
MBB: CESR131320---- _ _
ECB: CESR131249---- _ _
MARQ: CESR131171---- _ _
INDICATE UNIT SETTINGS BELOW
Control Type: Thermostat/T55 Space Temp./T--56 Space Temp./T--58 Space Temp.
Set Points: Cooling Occupied: _______________ Unoccupied: __________________
Heating Occupied: _______________ Unoccupied: __________________
Table 65 — MODE - CONFIGURATION
ITEM EXPANSION RANGE UNITS DEFAULT
CCN
TABLE/SUB --- TABLE
CCN POINT ENTRY
CONFIGURATION SERVICE
CONFIGURATION
DISP Display Configuration DISPLAY
METR Metric Display On/Off Off DISPUNIT
LANG Language Selection 0=English
1=Spanish
2=French
3=Portuguese
0 LANGUAGE
PROT Password Enable Enable/Disable Disable PASS_EBL
PSWD Service Password 0000 to 9999 1111 PASSWORD
TEST Test Display LEDs On/Off Off (display only, not in
table)
DISPTEST
UNIT Unit Configuration UNIT
S.DLY Startup Delay 0 to 600 sec 30 STARTDLY
OC.FN FanOnWhenOccupied Yes/ No Yes OCC_FAN
IDF.F Shut Down on IDF Failure Yes/ No Yes FATALFAN
FS.MX Supply Fan Maximum
Speed
80 to 100 % 100 SPEEDMAX
FS.MN Supply Fan Minimum Speed 10 to 40 % 20 SPEEDMIN
FS.VM Vent Mode Fan Speed 40 to 100 ^F 50 SPEEDVNT
FN.SW Fan Status Switch 0=No Switch
1=Normal Open
2=Normal Closed
0: no FIOP
1: FIOP
FANSTCFG
FL.SW Filter Status Switch 0=No Switch
1=Normal Open
2=Normal Closed
0: no FIOP
1: FIOP
FILSTCFG
FS.SW Fire Shutdown Switch 0=No Switch
1=Normal Open
2=Normal Closed
0: no FIOP
1: FIOP
SHTDNCFG
RM.SW Remote Occupancy Switch 0=No Switch
1=Normal Open
2=Normal Closed
0 REMOCCFG
RH.S RH Sensor on OAQ Input Yes/No No RH_OAQ
RH.SW Space Humidity Switch 0=No Switch
1=Normal Open
2=Normal Closed
0 HUMSTCFG
TCS.C Temp Cmp Strt Cool Factr 0to60 mins 0 TCSTCOOL
TCS.H TempCmpStrtHeatFactr 0to60 mins 0 TCSTHEAT
COOL Cooling Configuration COOL_CFG
MIN.C Min Compressor Capacity 15 to 80 % 70 MIN_CAPC
FS.CD Fan Speed Control Demand 1to9.9 ^F 3 SPEEDDMD
MRT.C Compressor Min On Time 120 to 999 sec 180 MIN_ON
MOT.C Compressor Min Off Time 300 to 999 sec 300 MIN_OFF
RST.C Runtime to Reset Strikes 120 to 999 sec 300 MIN_ON_S
FOD.C Fan--- off Delay, Mech Cool 0 to 600 sec 60 COOL_FOD
CS.A1 Current Sensing A1 Enable/Disable Disable: reserved for
future use
DO NOT ENABLE
A1_SENSE
C.LO Compressor Lockout Temp 0 to 100F dF 0 OATLCOMP
ALM.N Alert Each Strike Yes//No Ye s ALM_NOW
SAT Supply Air Temperature
SASP Cool Supply Air Setpoint 45 to 75 dF 65 SASP
SA.MU SASP Maximum Reset Up 0to20 ^F 10 SASPMAXU
SA.MD SASP Maximum Reset
Down
--- 2 0 t o 0 ^F --- 1 0 SASPMAXD
SAT.U Minimum SAT Upper Level 35.0 to 65.0 dF 60 SATMIN_H
SAT.L Minimum SAT Lower Level 35.0 to 65.0 dF 45 SATMIN_L
SST Low Suction Control
SST.O Suction OK Temperature 10 to 50 dF 18 SSTOK
SST.1 Low Suction --- Level 1 10 to 50 dF 20 SSTLEV1
SST.2 Low Suction --- Level 2 5to50 dF 15 SSTLEV2
SST.3 Low Suction --- Level 3 0to50 dF 10 SSTLEV3
PSI.D Ckt A Minimum Pressure 0 to 500 psig 20 DELTAP_A
OFC Outdoor Fan Control
1.MXP Fan Lev1 Max Pressure 100 to 500 psig 450 LEV1MAXP
2.MNP Fan Lev2 Min Pressure 100 to 500 psig 200 LEV2MINP
2.ON FanLev2OnTemperature 0 to 100 F 55 LEV2ON
2.OFF Fan Lev2 Off Temperature 0 to 100 F 45 LEV2OFF