109
APPENDIX A — LOCAL DISPLAY AND CCN TABLES (CONT)
MODE — CONFIGURATION (cont)
ITEM EXPANSION RANGE UNITS DEFAULT
CCN TABLE/
S U B --- T A B L E
CCN POINT PAGE NO.
HEAT Heating Configuration HEAT_CFG
HT.TY Type of Heat Installed 0=No Heat
1=Gas
2=Electric
0(50serieswithno
electric heat)
1(48series)
2(50serieswith
electric heat)
HEATTYPE 9
N.HTR Number of Heat Stages 1to2 1(48series
1--- phase, 50 series
<15kW)
2(48series
3--- phase, 50 series
>=15kW)
NUM_HEAT 9
MRT.H Heat Minimum On Time 60 to 999 sec 120 HMIN_ON 22
MOT.H Heat Minimum Off Time 60 to 999 sec 120 HMIN_OFF 22
H.DEC
Heat Stage Decrease
Time
120 to 999 sec 300 HSTAGDEC 21
H.INC
Heat Stage Increase
Time
120 to 999 sec 450 HSTAGINC 21
FOD.E Fan--- off Delay, Elect Heat 10 to 600 sec 30 ELEC_FOD 17
FOD.G Fan--- off Delay, Gas Heat 45 to 600 sec 45 GAS_FOD 17
HT.LO Heating Lockout Temp 40 to 125F dF 75 OATLHEAT 21
SAT
SAT.H SAT Heat Mode Sensing
Enable/Dis-
able
Disable SAT_HEAT 21
SAM.L
Maximum SAT Lower
Level
85 to 200 dF 140 SATMAX_L 21
SAM.U
Maximum SAT Upper
Level
85 to 200 dF 160 SATMAX_H 21
SPT Space Temperature
HT.PD
SPT Heat Demand (+)
Level
0.5 to 5 ^F 1 HDEM_POS
HT.ND
SPT Heat Demand (--- )
Level
--- 5 t o --- 0 . 5 ^F --- 1 HDEM_NEG
H.LAG Heat Thermal Lag Factor 0to5 min 1 HEAT_LAG
ECON
Economizer Configura-
tion
ECON_CFG
EC.EN Economizer Installed Yes/No No: no FIOP
Yes: FIOP
ECONO 23
E.CTL Economizer Control Type 1=Dig/Posi-
tion
2=Dig/Com-
mand
3=Analog
Ctrl
1 ECON_CTL 23
EC.MN Econo Minimum Position 0 to 100 % 30 ECONOMIN 31
EC.MX Econo Cool Max Position 0 to 100 % 100 ECONOMAX
23
M.ANG Min Actuator Ctrl Angle 75 to 90 88 MINANGLE 23
EH.LO
Econo Cool H i Temp Lim-
it
40 to 100F dF 65 OATLECLH 23
EL.LO
Econo Cool Lo Temp Lim-
it
--- 30 to 50F dF 0 OATLECLL 23
UEFC Unoccupied Free Cooling 0=Disabled
1=Unoccu-
pied
2=PreOc-
cupancy
2 UEFC_CFG 23
FC.TM Free Cool PreOcc Time 1 to 9999 min 120 UEFCTIME 23
FC.LO
Free Cool Low Temp Lim-
it
--- 30 to 70F dF 50 OATLUEFC 23
PE.EN Power Exhaust Installed Yes/No No: no FIOP
Yes: FIOP
PE_ENABL 24
PE.1
PE Stage1 Econo Posi-
tion
10 to 100 % 40 PE1_POS 24
PE.2
PE Stage2 Econo Posi-
tion
10 to 100 % 75 PE2_POS 24
EN.SW Enthalpy Switch 0=No Switch
1=Normal
Open
2=Normal
Closed
0: no FIOP
1: FIOP
ENTHLCFG 10
E.TRV Economizer Travel Time 5 to 300 sec 150 ECONOTRV
E.MXB Bottom Stage Max Econo 0 to 100 % 50 ECONMAXB
E.MXM Middle Stage Max Econo 1 to 100 % 35 ECONMAXM
E.MXT To p St a g e Ma x Eco n o 0 to 100 % 25 (PG03--- 16)
0 (20--- 28, PM16)
ECONMAXT
48/50PG and PM