APPENDIX A — LOCAL DISPLAY AND CCN TABLES (CONT)
MODE — CONFIGURATION (cont)
ITEM EXPANSION RANGE UNITS DEFAULT
CCN TABLE/
S U B --- T A B L E
CCN POINT PAGE NO.
AIR.Q Air Quality Config. IAQ_CFG
IA.CF IAQ Analog Input Config 0=No IAQ
1=DCV
2=Override
IAQ
3=Ctrl Min
Pos
0: no FIOP
1: FIOP
IAQANCFG 10
IA.FN IAQ Analog F an Config 0=Never
1=Occupied
2=Always
0 IAQANFAN 31
II.CF IAQ Switch Input Config 0=No IAQ
1=DCV N/O
2=DCV N/C
3=Override
N/O
4=Override
N/C
0 IAQINCFG 10
II.FN IAQ Switch Fan Config 0=Never
1=Occupied
2=Always
0 IAQINFAN 35
AQ.MN Econo Min IAQ Position 0 to 100 % 10 IAQMINP 31
EC.MN Econo Minimum Position 0 to 100 % 30 ECONOMIN 31
OVR.P IAQ Override Position 0 to 100 % 100 IAQOVPOS 31
OA.CF OAQ Analog Input Config 0=No OAQ
1=DCV
2=Lockout
OAQ
0 OAQANCFG 10
OAQ.L OAQ Lockout Limit 0 to 5000 600 OAQLOCK 34
AQD.L AQ Differential Low 0 to 5000 100 DAQ_LOW
AQD.H AQ Differential High 0 t o 5000 700 DAQ_HIGH
DF.ON FanOnAQDifferential 0 to 5000 600 DAQFNON 32
DF.OF Fan Off AQ Differential 0 to 5000 200 DAQFNOFF 32
I.4M IAQ Sensor Value at 4mA 0 to 5000 0 IAQ_ 4MA 28
I.20M
IAQ Sensor Value at
20mA
0 to 5000 2000 IAQ_20MA 28
O.4M
OAQ Sensor Value at
4mA
0 to 5000 0 OAQ_4MA 31
O.20M
OAQ Sensor Value at
20mA
0 to 5000 2000 OAQ_20MA
H.4M RH Sensor Value at 4mA 0to50 % 0 RH_4MA
H.20M RH Sensor Value at 20mA 60 to 100 % 100 RH _20MA
A.FAN Adaptive Fan AFAN_CFG
AF.EN Adaptive Fan Operation No/Yes No ADAPTFAN 12
FS.VN Fan Speed --- Ventilation 0 to 100 % 50 FSPDVENT 35
FS.AQ
Fan Speed --- IAQ Over-
ride
50 to 100 % 50 FSPDAQOR 35
FS.E1
Fan Speed --- Free Cool
Lo
50 to 100 % 60 FSPDECO1 35
FS.E2
Fan Speed --- Free Cool
Hi
90 to 100 % 90 FSPDECO2 35
FS.CL
Fan Speed --- Mech Cool-
ing
60 to 100 % 100 FSPDCOOL 35
FS.HT Fan Speed --- Heating 65 t o 100 % 100 FSPDHEAT 35
FS.RH Fan Speed --- Reheat2 65 to 100 % 100 FSPDREHT 35
ALM.O Alarm Relay Config. ALM_CFG 38
ALARM RELAY
ACTIVE FOR:
A.SPC SPT/SPRH Sensor Failure Yes/No Ye s SP ACE_AL
A.SRT SAT/RAT Sensor Failure Yes/No Ye s SATRAT AL
A.OAT OAT Thermistor Failure Ye s/No Yes OAT_AL
A.CS Current Sensor Failure Yes/No Yes CS_AL
A.CMP Compressor Failure Yes/No Ye s COMP_AL
A.CKT Refrig Circuit Failure Yes/No Yes CKT_AL
A.SSP SSP Transducer Failure Yes/No Yes SSP_AL
A.SCT SCT Thermistor Failure Yes/No Yes SCT_AL
A.FAN Indoor Fan Failure Yes/No Yes FAN_AL
A.FIL Dirty Filter Yes/No Yes FILT_AL
A.TST Thermostat Failure Yes/No Yes TSTAT_AL
A.ECO Economizer Failure Yes/No Ye s ECON_AL
PID PID Configurations PID_CFG
EC.P Economizer PID --- kP 0.00 to 99.90 sec 2.5 ECONO_P
EC.I Economizer PID --- kI 0.00 to 99.90 sec 0.12 ECONO_I
EC.D Economizer PID --- kD 0.00 to 99.90 sec 1 ECONO_D
EC.DT Economizer PID --- rate
10.00 to
180.00
sec 15 ECONO_DT
EC.DB
Economizer PID Dead-
band
0to25 % 3 ECONBAND
LK.P
Linkage Staging PID ---
kP
0.00 to 99.90 10 LINK_P
LK.I Linkage Staging PID --- kI 0.00 to 99.90 5 LINK_I
LK.D
Linkage Staging PID ---
kD
0.00 to 99.90 5 LINK_D
LK.DT
Linkage Staging PID ---
rate
10.00 to
180.00
secs 30 LINK_DT
48/50PG and PM