vent
air
needed
and
record
quantity
for
vent
adjustment
in
step
11.
5.
R
e
move
jumper
plug
from
base
unit
receptacle
and
discard.
Insert
economizer
plug
into
recep¬
tacle.
See
Fig.
15.
Steps
6
thru
8
involve
releasing
and
adjusting
indoor
damper
blades
from
factory
set
position.
Fig.
14
Outdoor
Air
Hood
Details
ECONOMIZER
PLUG
CLS
Cooling
Lockout
Switch
EC
Enthalpy
Control
OAT.
Outdoor
Air
Thermostat
OUTDOOR
AIR
INLET
SCREENS
(2)
Fig.
15
Economizer
Installed
in
Unit
6.
R
e
lease
indoor
blades’
drive
linkage
by
loosen¬
ing
linkage
connector
setscrew
at
indoor
crank-
arm
on
drive
shaft.
See
Fig.
16.
Remove
pink
wire
from
economizer
damper
motor
terminal
D
and
temporarily
tape
bare
wire
end.
Remove
violet
wire
from
economizer
damper
motor
and
connect
to
terminal
D
on
economizer
damper
motor.
See
Fig.
17.
OUTDOOR
BLADES(2)
DRIVE
SHAFT
OUTDOOR
DRIVE
LINKAGE
Fig.
16
INDOOR
BLADES
(3)
Economizer
Details
ECONOMIZER
DAMPER
MOTOR
PINK
WIRE
VIOLET
WIRE
TERMINAL
D
Fig.
17
Economizer
Motor
Connections
7.
Jumper
red
(base
unit
24-v
power)
and
black
(evaporator
fan
motor)
wires
in
24-volt
control
box
compartment.
See
Fig.
10.
Turn
on
base
unit
power
to
energize
evap¬
orator
fan.
The
economizer’s
outdoor
blades
should
open
completely.
8.
Adjust
the
indoor
blades’
drive
linkage
so
that
indoor
blades
are
fully
closed.
Tighten
the
linkage
connector
setscrew.
Turn
off
base
unit
power.
Reconnect
pink
and
violet
wires
to
economizer
motor,
as
shown
in
Fig.
17.
9.
If
vent
air
is
required,
leave
red
and
black
wires
jumpered.
If
vent
air
is
not
needed,
remove
jumper
between
red
and
black
wires.
10.
Fasten
baffle
to
left
side
of
damper
plate
with
round
head
screws
provided.
See
Fig.
18.
10