NOTES:
1. Weights include economizer (Std)
2. Center of gravity.
3. Do not locate adjacent units with dis-
charge facing economizer inlet. Mini-
mum clearances to be:
Adjacent Units: 158-09
Top of Units: No overhang
Outdoor Coil: 48-09
Economizer Side: 68-09
Filter Access Side: 108-09 (for re-
moval of evaporator coil)
4. For smaller service and operational
clearances, contact Carrier Applica-
tion Engineering department.
5. Bottom ducts designed to be attached
to accessory roof curb. If unit is mounted
on dunnage, it is recommended the
ducts be supported by cross braces as
done on accessory roof curb.
6. Dimensions are in inches. Dimen-
sions in [ ] are in millimeters.
7. For units with electric heat, a field-
supplied 90° elbow must be installed
in the supply ductwork below the unit
discharge.
UNIT SIZE
50EJQ
OPERATING
WEIGHT
(lb)
AB
CORNER WEIGHT
(lb)
ft-in. ft-in. 1 2 3 4
024 4168 5-7
3
⁄
8
3-7
5
⁄
8
843 859 1245 1222
028 4168 5-7
3
⁄
8
3-7
5
⁄
8
843 859 1245 1222
Fig. 2 — Base Unit Dimensions, 50EJQ024 and 028
3