Refrigerant
These units are supplied with one of these refrigerants:
R-410A: belongs to the A1/A1 group, i.e. with high safety both
in the mix and also in the case of a leak.
R-454B: belongs to the A2L group, that is, non-toxic and low
ammability.
Caution: with A2L refrigerant, always use an A2L refrigerant
detector when near the unit.
Important: the type of refrigerant included in the unit can be
consulted on the name plate, see section 4.3.
Note: These units are prepared for the replacement of R-410A
refrigerant by R454B on site. The necessary elements for this
change are supplied in a kit. All the instructions for carrying out
this retro t are explained in a separate document (N10692).
Periodic check of tightness:
Only quali ed personnel must perform a periodic leak testing, in
accordance with the regulation (EC) No. 517/2014.
The frequency of checks is no longer related to the refrigerant
charge but to its global warming potential:
Charge kg x GWP = t CO2e
Carbon dioxide equivalency (t CO2e) is a quantity that
describes, for a given mixture and amount of greenhouse gas,
the amount in tonnes of CO
2
that would have the same global
warming potential (GWP).
Operators shall ensure that the unit is checked for leaks ad
minima according to the following frequency:
Main circuits:
R-410A
Cooling recovery circuit (optional):
Equivalent charge
(kg)
Frequency
(months)
Environ. impact
(Equiv. tonnes)
R-410A R-454B
With
detector
Without
detector
t CO2e < 5 2,4 10,8 not subject to revision
t CO2e 5 to 50 2,4 10,8 24 12
t CO2e 50 to 500 23,9 108,5 12 6
t CO2e > 500 239,5 1084,6 6 3
Important: units with A2L refrigerant are always equipped
with a leak detector with infrared sensor. Consult the
chapter “Safety elements”.
The following table shows the refrigerant charge and CO
2
equivalent tonnes (t CO2e) for each model:
14 - MAINTENANCE
Filter drier
The lter function is the preserve the cooling circuit clean and
without humidity, neutralizing the acids that can be found in
the cooling circuit.
Measure the di erence in the temperature of the pipes at the
drier inlet and outlet.
If necessary, replace.
Charging valve
Filter drier
50FC 100 110 120 130 145 160
Charge
(kg)
C1: 17,0
C2: 17,0
C1: 17,0
C2: 17,0
C1: 17,0
C2: 17,0
C1: 18,5
C2: 18,5
C1: 18,5
C2: 18,5
C1: 18,8
C2: 18,8
Environ.
impact
(t CO2e)
C1: 35,5
C2: 35,5
C1: 35,5
C2: 35,5
C1: 35,5
C2: 35,5
C1: 38,7
C2: 38,7
C1: 38,7
C2: 38,7
C1: 39,2
C2: 38,7
50FC 170 180 200 220 250 280
Charge
(kg)
C1: 19,0
C2: 19,0
C1: 28,3
C2: 28,3
C1: 29,3
C2: 29,3
C1: 29,3
C2: 29,3
C1: 37,0
C2: 37,0
C1: 37,5
C2: 37,5
Environ.
impact
(t CO2e)
C1: 39,7
C2: 39,7
C1: 59,0
C2: 59,0
C1: 61,1
C2: 61,1
C1: 61,1
C2: 61,1
C1: 77,3
C2: 77,3
C1: 78,3
C2: 78,3
50FC 100 110 120 130 145 160
Charge
(kg)
C3: 5,3 C3: 5,3 C3: 5,3 C3: 6,4 C3: 6,4 C3: 6,4
Environ.
impact
(t CO2e)
C3: 11,1 C3: 11,1 C3: 11,1 C3: 13,4 C3: 13,4 C3: 13,4
50FC 170 180 200 220 250 280
Charge
(kg)
C3: 6,4 C3: 7,6 C3: 7,6 C3: 7,6 C3: 11,9 C3: 11,9
Environ.
impact
(t CO2e)
C3: 13,4 C3: 15,9 C3: 15,9 C3: 15,9 C3: 24,8 C3: 24,8
50FF/FC 100 110 120 130 145 160
Charge
(kg)
C1: 15,5
C2: 15,5
C1: 15,5
C2: 15,5
C1: 15,5
C2: 15,5
C1: 17,0
C2: 17,0
C1: 17,0
C2: 17,0
C1: 17,3
C2: 17,3
Environ.
impact
(t CO2e)
C1: 7,2
C2: 7,2
C1: 7,2
C2: 7,2
C1: 7,2
C2: 7,2
C1: 7,9
C2: 7,9
C1: 7,9
C2: 7,9
C1: 8,0
C2: 8,0
Main circuits:
50FF/FC 170 180 200 220 250 280
Charge
(kg)
C1: 17,5
C2: 17,5
C1: 24,5
C2: 24,5
C1: 25,5
C2: 25,5
C1: 25,5
C2: 25,5
C1: 30,5
C2: 30,5
C1: 31,0
C2: 31,0
Environ.
impact
(t CO2e)
C1: 8,2
C2: 8,2
C1: 11,4
C2: 11,4
C1: 11,9
C2: 11,9
C1: 11,9
C2: 11,9
C1: 14,2
C2: 14,2
C1: 14,4
C2: 14,4
Cooling recovery circuit (optional):
50FF/FC 100 110 120 130 145 160
Charge
(kg)
C3: 4,8 C3: 4,8 C3: 4,8 C3: 5,8 C3: 5,8 C3: 5,8
Environ.
impact
(t CO2e)
C3: 2,2 C3: 2,2 C3: 2,2 C3: 2,7 C3: 2,7 C3: 2,7
50FF/FC 170 180 200 220 250 280
Charge
(kg)
C3: 5,8 C3: 6,8 C3: 6,8 C3: 6,8 C3: 10,7 C3: 10,7
Environ.
impact
(t CO2e)
C3: 2,7 C3: 3,2 C3: 3,2 C3: 3,2 C3: 5,0 C3: 5,0
R-454B

Other manuals for Carrier 50FC Series

Related product manuals