EasyManua.ls Logo

Carrier 50HJ015 - Service; Awarning; Before Performing Service or Maintenance Operations; Shock Could Cause Personal Injury

Carrier 50HJ015
18 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table
7
-
Accessory/FlOP
Static
Pressure
Drop*
(in.
wg)
UNIT
50HJ
UNIT
VOLTAGE
208/230-3-60
015
460-3-60
575-3-60
208/230-3-60
024
460-3-60
575-3-60
CFM
4,000
5,000
6,000
7,200
4,000
5,000
6,000
7,200
4,000
5,000
6,000
7,200
0
05
0.07
0
09
ELECTRIC
HEATERS
(kW)
(14-34)
0
06
(42)
0
07
(56)
14-34
0.08
42
0.10(56
(14-34)
0
12
(42)
0.15
(56)
El
05
(15,32)
0.06
(55)
0
07
15,32
0
08
(55)
0
09
(15,32)
012
55)
0.06
(37)
0
08
37)
0
12
37
0
15
37)
ECONOMIZER
0^3
0
05
0.07
0
09
0
03
0
05
0.07
0
09
0
03
0.05
0
07
0
09
6,000
0
09
(26/34)
0
12
(42/56)
0
15
56/75
0
07
7,200
0
11
26/34
0
16
42/56
0
20
56/75
0
09
9,000
0
15
26/34
0
19
42/56
0
24
56/75
0.11
10,000
0.17
26/34
0.21
(42/56)
0.26
(56/75)
0
12
6,000
7,200
9,000
10,000
0.09
(32)
0.12
(55)
0.15
(80)
0
11
32
0.15
(55
0
20
80
0
15
(32
0
19
55
0
24
(80
0.17(32)
0
21
(55)
0.26
(80)
6,000
_
7,200
9,000
10,000
0
07
0
09
0.11
0.12
0
07
0
09
0.11
0
12
FIOP
Factory-Installed
Option
NOTE:
Heaters
are
rated
at
208/240
v,
480
v,
and
575
v
"The
static
pressure
must
be
added
to
external
static
pressure
The
sum
and
the
evaporator
entering
air
cfm
should
then
be
used
in
conjunction
with
the
Fan
Performance
table
to
determine
blower
rpm
and
watts
SERVICE
A
WARNING
Before
performing
service
or
maintenance
operations
on
unit,
turn
off
main
power
switch
to
unit.
Turn
off
accessory
heater
power
switch
if
applicable.
Electrical
shock
could
cause
personal
injury.
Cleaning
Inspect
unit
interior
at
beginning
of
each
heating
and
cooling
season
and
as
operating
conditions
re¬
quire.
Remove
unit
top
panel
and/or
side
panels
for
access
to
unit
interior.
EVAPORATOR
COIL
Clean
as
required
with
a
com¬
mercial
coil
cleaner.
CONDENSER
COIL
Clean
condenser
coil
annually
and
as
required
by
location
and
outdoor-air
conditions.
Inspect
coil
monthly
clean
as
required.
CONDENSATE
DRAIN
Check
and
clean
each
year
at
start
of
cooling
season.
FILTERS
Clean
or
replace
at
start
of
each
heating
and
cooling
season,
or
more
often
if
operating
conditions
re¬
quire.
Refer
to
Table
1
for
type
and
size.
OUTDOOR-AIR
INLET
SCREENS
Clean
screens
with
steam
or
hot
water
and
a
mild
detergent.
Do
not
use
dis¬
posable
filters
in
place
of
screens.
Lubrication
COMPRESSORS
Each
compressor
is
charged
with
cor¬
rect
amount
of
oil
at
the
factory.
Observe
the
oil
level
in
the
sight
glass
at
start-up.
If
unit
oil
level
is
below
sight
glass,
add
oil
until
level
is
approximately
l
A
sight
glass.
FAN
SHAFT
BEARINGS
The
bearings
are
of
the
pil¬
low
block
type
and
have
grease
fittings.
The
bearing
oppo¬
site
the
motor
end
has
an
extended
tube
line
so
it
can
be
lubricated
from
the
motor
side.
Lubricate
the
bearings
twice
annually.
Typical
lubricants
are
given
below:
MANUFACTURER
LUBRICANT
Texaco
Reqal
AFB-2*
Mobil
Mobilplex
EP
No.
1
Sunoco
Prestige
42
Texaco
Multifak
2
‘Preferred
lubricant
because
it
contains
rust
and
oxidation
inhibitors
CONDENSER
AND
EVAPORATOR-FAN
MOTOR
BEAR¬
INGS
The
condenser
and
evaporator-fan
motors
have
permanently-sealed
bearings,
so
no
field
lubrication
is
necessary.
Evaporator
Fan,
50HJ015
Units
PERFORMANCE
ADJUSTMENT
Fan
motor
pulleys
on
the
50HJ015
units
are
factory
set
for
speed
shown
in
Table
I.
To
change
fan
speeds:
1.
Shut
off
unit
power
supply.
2.
Loosen
belt
by
loosening
fan
motor
mounting
plate
nuts.
3.
Loosen
movable-pulley
flange
setscrew
(see
Fig.
19).
4.
Screw
movable
flange
toward
fixed
flange
to
increase
speed
and
away
from
fixed
flange
to
deccrease
speed.
Increasing
fan
speed
increases
load
on
motor.
Do
not
exceed
maximum
speed
specified
in
Table
1.
5.
Set
movable
flange
at
nearest
key
way
of
pulley
hub
and
tighten
setscrew.
(See
Table
1
for
speed
change
for
each
full
turn
of
pulley
flange.)
To
align
fan
and
motor
pulleys:
1.
Loosen
fan
pulley
setscrews.
2.
Slide
fan
pulley
along
fan
shaft.
3.
Make
angular
alignment
by
loosening
motor
from
mount¬
ing
plate.
SERVICE
AND
REPLACEMENT
(see
Fig.
20)
NOTE:
To
remove
belts
only,
follow
Steps
1-7.
1.
Remove
filter
and
supply-air
section
panels.
2.
Remove
unit
to
cover.
3.
Remove
coil
guard.
4.
Loosen
screws
A
and
B
on
both
sides
of
motor
mount
assembly.
5.
Loosen
screw
C.
6.
Rotate
motor
mount
assembly
(with
motor
attached)
as
far
as
possible
away
from
evaporator
coil.
7.
Remove
belt.
12

Related product manuals