EasyManua.ls Logo

Carrier 50HJ015 - Start-Up

Carrier 50HJ015
18 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
START-UP
Use
the
following
information
and
Start-Up
Checklist
on
page
CL-1
to
check
out
unit
PRIOR
to
start-up.
Unit
Preparation
Check
that
unit
has
been
installed
in
accordance
with
these
installation
instructions
and
all
applicable
codes.
Compressor
Mounting
Loosen
compressor
hold¬
down
bolts
until
sideways
movement
of
the
washer
under
each
holddown
bolt
head
can
be
obtained.
Do
not
loosen
completely,
as
bolts
are
self-locking
and
will
main¬
tain
adjustment.
Internal
Wiring
Check
all
electrical
connections
in
unit
control
boxes;
tighten
as
required.
Refrigerant
Service
Ports
and
Valves
Each
50HJ
unit
has
2
Schrader-type
service
ports
per
circuit;
one
on
the
suction
line
and
one
on
the
liquid
line.
Be
sure
that
the
caps
on
the
ports
are
tight.
The
units
also
have
2
service
valves
per
circuit;
one
on
the
suction
line
and
one
on
the
discharge
line.
Be
sure
all
valves
are
open.
Crankcase
Heaters
Heaters
are
energized
as
long
as
there
is
power
to
unit.
IMPORTANT:
Unit
power
must
be
on
for
24
hours
prior
to
start-up.
Otherwise,
damage
to
compressor
may
result.
Evaporator
Fan
Fan
belt
and
pulleys
are
factory
in¬
stalled.
Remove
tape
from
the
fan
pulley
and
adjust
pulleys
on
50HJ015
units
as
required.
See
Evaporator-Fan
Perfor¬
mance
Adjustment
section
on
page
12.
See
Table
4
for
Air
Quantity
Limits.
See
Tables
5,
6A,
and
6B
for
Fan
Perfor¬
mance
data.
Be
sure
that
fans
rotate
in
the
proper
direction.
See
Table
7
for
Static
Pressure
Drops
for
accessories
and
options.
To
alter
fan
performance,
see
Evaporator-Fan
Per¬
formance
Adjustment
sections,
pages
12
and
13.
Table
4
Air
Quantity
Limits
UNIT
50HJ
MINIMUM
CFM
MAXIMUM
CFM
015
3750
6,250
024
6000
10,000
Condenser
Fans
and
Motors
Fans
and
motors
are
factory
set.
Refer
to
Service,
Condenser-Fan
Adjust¬
ment
section
as
required.
Return-Air
Filters
Check
that
correct
filters
are
installed
in
filter
tracks.
See
Table
1.
Do
not
operate
unit
without
return-air
filters.
Outdoor-Air
Inlet
Screens
Outdoor-air
inlet
screens
must
be
in
place
before
operating
unit.
Accessory
Field-Installed
Economizer
Adjust¬
ment
Remove
filter
access
panel.
Check
that
outdoor-
air
damper
is
closed
and
return-air
damper
is
open.
Economizer
operation
and
adjustment
is
described
in
Start-Up,
Base
Unit
Operation;
and
Service,
Economizer
Adjustment
sections,
respectively.
Base
Unit
Operation
COOLING,
UNITS
WITHOUT
ECONOMIZER
-
When
thermostat
calls
for
cooling,
terminals
G
and
Y1
are
ener¬
gized.
The
indoor
(evaporator)
fan
contactor
(IFC)
and
com¬
pressor
contactor
no.
1
(Cl)
are
energized
and
evaporator-
fan
motor,
compressor
no.
1
(024)
or
unloaded
compressor
(015),
and
condenser
fans
start.
The
condenser-fan
motors
run
continuously
while
unit
is
cooling.
If
the
thermostat
calls
for
a
second
stage
of
cooling
by
energizing
Y2,
compressor
contactor
no.
2
(C2)
is
energized
and
compressor
no.
2
starts
(024),
or
compressor
no.
1
runs
fully
loaded
(015).
A
freeze
protection
thermostat
(FPT)
is
located
on
the
evaporator
coil.
It
detects
frost
buildup
and
turns
off
the
compressors,
allowing
the
coil
to
clear.
Once
frost
has
melted,
the
compressors
can
be
reenergized
by
resetting
the
thermostat.
HEATING,
UNITS
WITHOUT
ECONOMIZER
(If
Acces¬
sory
or
Optional
Heater
is
Installed)
Upon
a
call
for
heating
through
terminal
Wl,
IFC
and
heater
contactor
no.
1
(HC1)
are
energized.
On
units
equipped
for
2
stages
of
heat,
when
additional
heat
is
needed,
HC2
is
energized
through
W2.
COOLING,
UNITS
WITH
ECONOMIZER
-
Upon
a
call
for
cooling,
when
outdoor
ambient
temperature
is
above
the
outdoor-air
temperature
control
setting,
the
evaporator
and
condenser
fans
and
compressor
energize.
The
economizer
damper
moves
to
VENT
position.
Upon
a
first-stage
call
for
cooling,
when
outdoor
ambi¬
ent
temperature
is
below
the
temperature
control
setting,
the
evaporator
fan
starts
and
economizer
damper
modulates
to
maintain
mixed-air
temperature.
The
compressor(s)
re¬
mains
off.
Upon
a
second-stage
call
for
cooling,
compressor
no
1
(024)
or
unloaded
compressor
(015)
is
energized
and
me¬
chanical
cooling
is
integrated
with
economizer
cooling
Com¬
pressor
no.
2
(024
only)
is
locked
out.
If
the
outdoor-air
temperature
is
below
50
F,
a
cooling
lockout
switch
prevents
the
compressor(s)
from
running.
When
supply-air
temperature
drops
below
a
fixed
set
point,
the
economizer
damper
modulates
to
maintain
the
temper¬
ature
at
the
fixed
set
point.
HEATING,
UNITS
WITH
ECONOMIZER
(If
Accessory
or
Optional
Heater
is
Installed)
The
outdoor
air
damper
stays
at
VENT
position
while
the
evaporator
fan
is
operat¬
ing
Upon
a
call
for
heating
through
terminal
Wl,
the
in¬
door
(evaporator)
fan
contactor
(IFC)
and
heater
contactor
no.
1
(HC1)
are
energized.
On
units
equipped
for
2
stages
of
heat,
when
additional
heat
is
needed,
HC2
is
energized
through
W2.
10

Related product manuals