EasyManua.ls Logo

Carrier 50HJ015 - Step 7 - Make Outdoor-Air Inlet; Adjustments; Manual Outdoor-Air Damper; Optional Factory-Installed

Carrier 50HJ015
18 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table
2
Electrical
Data
UNIT
50HJ
V-PH-HZ
VOLTAGE
RANGE
COMPRESSOR
CONDENSER
FAN
MOTOR
EVAPORATOR
FAN
MOTOR
ACCESSORY/OPTIONAL
ELECTRIC
HEATERS*
POWER
SUPPLY
No.
1
No.
2
Min
Max
RLA
LRA
RLA
LRA
Qty
FLA
Hp
FLA
FLA
kW
MCA
MOCPf
015
208/230-3-60
187
253
49
3
191
-
-
2
77
3
105
39/
45
72/
82
117/135
14/19
26/34
42/56
88/
88
88/
88
103/116
159/148
100/100
100/100
110/125
175/175
460-3-60
414
508
22
1
86
-
-
2
33
3
48
18
39
66
15
32
55
39
39
55
72
45
45
60
80
575-3-60
518
632
179
69
-
-
2
26
3
39
37
37
32
52
35
60
024
208/230-3-60
187
253
43
9
170
43
9
170
2
54
(ea)
7%
24
2/22
0
72/
82
117/135
156/180“
26/34
42/56
56/75“
134/132
134/132
177/163
186/208“
175/175
175/175
200/175
200/225“
460-3-60
414
508
199
77
19
9
77
2
27
(ea)
7
Vs
11
0
39
66
96“
32
55
80“
62
62
80
110“
80
80
90
110“
575-3-60
518
632
159
62
159
62
2
34
(ea)
7
Vs
9
0
-
-
52
60
LEGEND
FLA
Full
Load
Amps
HACR
Heating,
Air
Conditioning
and
Refrigeration
LRA
Locked
Rotor
Amps
MCA
Minimum
Circuit
Amps
MOCP
Maximum
Overcurrent
Protection
NEC
National
Electrical
Code
RLA
Rated
Load
Amps
‘Heater
capacity'
(kW)
is
based
on
heater
voltage
of
208
v,
240
v,
480
v
and
575
v.
If
power
distribution
voltage
to
unit
varies
from
rated
heater
voltage,
heater
kW
will
vary
accordingly
This
is
the
maximum
size
permissible;
smaller
fuse
size
may
be
used
where
conditions
permit
tFuse
or
HACR
circuit
breaker
“Heaters
are
field
installed
only
NOTES:
1.
In
compliance
with
NEC
requirements
for
multimotor
and
combination
load
equipment
(refer
to
NEC
Articles
430
and
440),
the
overcurrent
protective
device
for
the
unit
shall
be
fuse
or
HACR
breaker
The
Canadian
units
may
be
fuse
or
circuit
breaker
2
MCA
calculation
for
units
with
electric
heaters
over
50
kW
=
(1.25
x
IFM
amps)
+
(1
00
x
heater
FLA).
Table
3
-
Heat
Anticipator
Settings
UNIT
VOLTAGES
kW
STAGE
1
STAGE
2
14/17
40
208/230
26/31
40
40
50HJ
42/52
66
40
15
40
Ol
5
460
30
40
40
51
40
66
575
37
40
.66
26/31
40
66
208/230,575-3-60
42/52
.66
40
50HJ
56/69
66
66
024
30
40
40
460-3-60
51
40
66
_73_j
66
66
Step
7
Make
Outdoor-Air
Inlet
Adjustments
MANUAL
OUTDOOR-AIR
DAMPER
-
All
units
(except
those
equipped
with
a
factory-installed
economizer)
have
a
manual
outdoor-air
damper
to
provide
ventilation
air.
Damper
can
be
preset
to
admit
up
to
25%
outdoor
air
into
return-air
compartment.
To
adjust,
loosen
securing
screws
and
move
damper
to
desired
setting
Then
retighten
screws
to
secure
damper
(Fig.
12).
OPTIONAL
FACTORY-INSTALLED
ECONOMIZER
Economizer
Motor
Control
Module
(Fig.
13-15)
Set
to
the
"D"
setting
(Fig.
14)
The
control
module
is
located
on
the
economizer
motor.
See
Fig.
13
and
15.
Damper
Vent
Position
Setting
1.
Set
fan
switch
at
ON
position
(continuous
fan
operation)
and
close
night
switch
if
used.
2.
Set
system
selector
switch
to
OFF
position.
3.
Turn
adjustment
screw
slowly
until
dampers
assume
de¬
sired
vent
position.
Do
not
manually
operate
econo¬
mizer
motor
since
damage
to
motor
will
result.
NOTE:
Refer
to
accessory
installation
instructions
in¬
cluded
with
the
field-installed
economizer
for
installation
information.
Also
see
Accessory
Field-Installed
Econo¬
mizer
Adjustment
section
on
page
10.
Step
8
Install
Outdoor-Air
Hood
The
same
type
of
factory-installed
hood
is
used
on
units
with
25%
air
ventilation
and
units
with
an
economizer.
NOTE:
The
hood
top
panel,
upper
and
lower
filter
retain¬
ers,
hood
drain
pan,
baffle
(024
only),
and
filter
support
bracket
are
secured
opposite
the
condenser
end
of
the
unit.
The
screens,
hood
side
panels,
remaining
section
of
filter
support
bracket,
seal
strip,
and
all
other
hardware
are
in
a
package
located
inside
the
return-air
filter
access
panel
(Fig.
16)
1.
Attach
seal
strip
to
upper
filter
retainer.
See
Fig.
17.
2.
Assemble
hood
top
panel
and
side
panels,
upper
filter
retainer,
and
hood
drain
pan
(Fig.
18)
3.
Secure
lower
filter
retainer
and
long
piece
of
filter
sup¬
port
bracket
to
unit.
See
Fig.
18.
Leave
screws
on
024
units
loose
4.
50HJ024
Units
Only:
Slide
baffle
behind
lower
filter
re¬
tainer
and
tighten
screws.
5.
Loosen
sheet
metal
screws
for
base
unit
top
panel
lo¬
cated
above
outdoor-air
inlet
opening.
25%
ADJUSTABLE
AIR
DAMPER
BASE
UNIT
Fig.
12
25%
Outdoor-Air
Section
Details

Related product manuals