11
52VCR,VER UNITS (208/230 V-1 Ph-60 Hz)
LEGEND
UNIT SIZE
BLOWER
DATA
CONDENSER
DATA
ELECTRIC HEAT DATA
MCA MOCP
Evaporator
Motor
Compressor
Condenser
Motor
Heater
Type
kW
Total
Heating
Amps
Amps Hp RLA LRA FLA Hp 230v 208v230v 208v230v 208v230v 208v
09 0.72
1
/
8
4.4 25 0.50
1
/
15
00 7 7 15 15
02 2 1.5 6,800 5,100 10 12 15 15
03 3 2.25 10,200 7,700 15 17 15 20
04 4 3 13,600 10,200 19 22 20 25
12 0.72
1
/
8
5.6 29 0.72
1
/
10
00 9 9 15 15
02 2 1.5 6,800 5,100 10 12 15 15
03 3 2.25 10,200 7,700 15 17 15 20
04 4 3 13,600 10,200 19 22 20 25
05 4.5 3.38 15,350 11,500 22 25 25 25
18 0.87
1
/
8
6.5 43 0.72
1
/
10
00 12 12 20 20
03 3 2.25 10,200 7,700 15 17 20 20
04 4 3 13,600 10,200 19 22 20 25
05 4.5 3.38 15,350 11,500 22 25 25 25
06 6 4.5 20,500 15,350 28 33 30 35
0886.0 27,300 20,500 37 43 40 45
10 9 6.75 30,700 23,000 42 48 45 50
24 2.8
1
/
3
9.9 54 0.74
1
/
8
00 17 17 20 20
03 3 2.25 10,200 7,700 17 19 20 20
04 4 3 13,600 10,200 21 24 25 25
05 4.5 3.38 15,350 11,500 24 27 25 30
06 6 4.5 20,500 15,350 30 35 30 35
0886.0 27,300 20,500 39 45 40 45
10 9 6.75 30,700 23,000 44 50 45 50
FLA Full Load Amps
HP Horsepower
LRA Locked Rotor Amps
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection
RLA Rated Load Amps
Electrical data