2
Low ambient lockout locks out com-
pressor at ambient temperatures below 
40 F to extend compressor life.
Random restart is used when power 
is turned on after a power outage. A 
built-in random restart (3 to 4 minutes) 
prevents all the compressors from re-
starting simultaneously.
Compressor restart delay of 3 min-
utes ensures that system pressures are 
allowed to equalize before a compres-
sor restart, which extends compressor 
life.
Front desk control allows the user, 
when the unit is wired to a front desk 
console, to enable or disable each unit 
from the front desk, thus saving the en-
ergy used to condition unoccupied 
rooms.
Fan delay allows the evaporator blow-
er to continue running for up to        
45 seconds after the thermostat is sat-
isfied. This feature maximizes cooling 
performance.
Ease of service
A service pullout is factory installed for 
service convenience and maintenance.
  Filter brackets and throwaway filter 
are shipped with each unit and are field 
installed over the unit’s evaporator 
coil. Filter size is 18 x 24 x 1-inch.
Adjustable operation
An adjustable fresh air (manual) damp-
er can be used to meet code require-
ments for fresh air introduction. When 
opened, the fresh air vent allows up to 
50 cfm of outside air to be introduced 
into the equipment closet. The air then 
mixes with return air entering the clos-
et through the return-air grille. See Ap-
plication Data section for more          
information.
Thermostat control
The 52V unit is easily controlled by a 
standard low voltage wall-mounted 
thermostat instead of complicated unit-
mounted controls. Low voltage wires 
are routed out the left side of the     
cabinet.
Easy installation
Rear or side installation wall sleeves 
are provided for pre-installation. When 
ready, the 52V unit is simply slid into 
the sleeve and the ductwork and elec-
trical are connected.
  The sleeve is weight-bearing and sup-
ports the entire weight of the 52V unit. 
The sleeve provides a weather tight 
seal against wind and water infiltration. 
A 
3
/
4
-in. male NPT fitting is provided 
in the bottom of the sleeve for field 
connection to a condensate riser.
  Four wall sleeve depths are available 
to accommodate wall thickness from 5 
to 20 inches. Each sleeve includes a 
factory-installed weather guard to     
cover the sleeve opening during 
construction.
Unique sleeve drain conden-
sate system
A factory-installed drain line connects 
the evaporator drain pan to a vertical 
pipe connection in the 52V basepan. 
Evaporator condensate is delivered 
from the unit to a catch tray in the wall 
sleeve and exits the sleeve through the 
3
/
4
-in. male NPT fitting.
  This design allows the plumber to 
completely pipe the drain to a conden-
sate riser during the pre-installation 
stage, thus decreasing the likelihood of 
condensate connection problems usu-
ally encountered when trying to con-
nect the HVAC (heating, ventilation, 
and air conditioning) condensate drain 
to the riser after the HVAC unit is in-
stalled in the closet.
  This feature also allows the 52V unit 
to be removed for service without 
disconnecting the condensate piping. 
This configuration does not require any 
additional closet space to make the 
drain connection, as do some competi-
tive products.
Redundant systems
If for any reason the primary conden-
sate riser becomes clogged, water will 
fill the catch tray and then be diverted 
through the sleeve to the exterior of 
the building, in a secondary system, 
rather than be allowed to overflow into 
the closet or living area. Rain water en-
tering the sleeve is automatically divert-
ed to the building exterior as well.
Return air options
Ductable return air tabs are provided 
on the inlet of the evaporator coil to 
permit the connection of return air 
ductwork if required by local codes.  
Please note that most installations 
would not normally require ducted re-
turn air.
Attractive appearance
The new flush-style architectural louver 
is an attractive extruded aluminum ar-
chitectural louver that attaches to the 
outside face of the wall sleeve. The 
blades of the grille recess into the wall 
sleeve for a neat, flush appearance. 
Louvers install from the inside of the 
wall sleeve. The 52V unit should not 
be installed into the sleeve before in-
stalling the louver.
Features/Benefits (cont)
Table of contents
Page
Features/Benefits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-3 
Model Number Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Capacity Ratings  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  4,5
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Field-Installed Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Base Unit Dimensions  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  7,8
Accessory Dimensions  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11,12
Typical Wiring Schematic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Controls  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14,15
Typical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Application Data  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18,19