10
AIR DELIVERY -- CFM (With Filter)*
Unit Size Operating Mode
CFM
Airflow
Setting
External
Static
Pressure
Range*
(in. wc)
External Static Pressure (ESP) (IN WC)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
070---12 AIRFLOW (CFM)
†† Low Heat 735 (615) 0---0.50 735 735 735 735 725
High Heat 1180 (1060) 0 --- 1 . 0 1160 1165 1175 1180 1180 1180 1180 1180 1180 1175
†† 1 --- 1 / 2 --- To n C o o l i n g 525 0 ---0.50‡ 515 500 500 490 485
†† 2 --- To n A / C C o o l i n g 700 0 ---0.50‡ 690 680 675 680 675
2 --- 1 / 2 --- To n A / C C o o l i n g 875 0---1.0‡ 875 875 875 870 865 855 850 835 825 820
3 --- To n A / C C o o l i n g 1050 0 ---1.0‡ 1050 1050 1050 1050 1050 1050 1045 1035 1020 1000
3 --- 1 / 2 --- To n A / C C o o l i n g 1225 0 --- 1 . 0 1220 1225 1225 1225 1225 1220 1205 1190 1185 1170
Maximum 1400 0 --- 1 . 0 1395 1400 1400 1400 1395 1385 1370 1340 1300 1245
090---16
Low Heat 985 (825)† 0 --- 1 . 0 950 970 985 985 985 985 985 985 985 980
High Heat 1210 (1090) 0 --- 1 . 0 1190 1205 1210 1210 1210 1210 1210 1210 1210 1200
†† 1 --- 1 / 2 --- To n A / C C o o l i n g 525 0 ---0.50‡ 525 520 525 495 475
†† 2 --- To n A / C C o o l i n g 700 0 ---0.50‡ 680 680 680 675 670
2 --- 1 / 2 --- To n A / C C o o l i n g 875 0---1.0‡ 815 845 845 855 850 850 845 835 820 805
3 --- To n A / C C o o l i n g 1050 0 ---1.0‡ 1005 1005 1015 1035 1040 1040 1035 1030 1025 1010
3 --- 1 / 2 --- To n A / C C o o l i n g 1225 0 --- 1 . 0 1190 1200 1200 1205 1205 1215 1205 1200 1185 1170
4 --- To n A / C C o o l i n g 1400 0 --- 1 . 0 1350 1370 1390 1390 1400 1390 1380 1380 1360 1340
Maximum 1600 0 --- 1 . 0 1595 1600 1600 1600 1595 1555 1505 1465 1430 1390
110---20***
Low Heat 1320 (1110)† 0 --- 1 . 0 1275 1295 1315 1320 1320 1320 1320 1320 1320 1315
High Heat 1475 (1330) 0 --- 1 . 0 1460 1465 1475 1475 1475 1475 1475 1475 1465 1465
†† 2 --- To n A / C C o o l i n g 700 0 ---0.50‡ 700 700 700 700 700
†† 2 --- 1 / 2 --- To n A / C C o o l i n g 875 0 ---0.50‡ 875 875 875 875 875
†† 3 --- To n A / C C o o l i n g 1050 0---0.50‡ 1050 1050 1050 1050 1050
3 --- 1 / 2 --- To n A / C C o o l i n g 1225 0 ---1.0‡ 1225 1225 1225 1225 1225 1225 1225 1225 1225 1225
4 --- To n A / C C o o l i n g 1400 0 ---1.0‡ 1400 1400 1400 1400 1400 1400 1400 1400 1400 1400
5 --- To n A / C C o o l i n g 1750 0 ---1.0‡ 1750 1750 1750 1750 1750 1750 1750 1750 1740 1725
6 --- To n A / C C o o l i n g 2100 0 --- 1 . 0 2100 2100 2100 2100 2090 2075 2055 2040 2005 1970
Maximum 2200 0 --- 1 . 0 2200 2190 2190 2180 2155 2145 2125 2100 2080 2020
135---22
Low Heat 1700 (1430)† 0 --- 1 . 0 1700 1700 1700 1700 1700 1695 1700 1695 1685 1670
High Heat 1915 (1725) 0 --- 1 . 0 1900 1905 1915 1915 1915 1915 1915 1915 1915 1915
†† 2 --- To n A / C C o o l i n g 700 0 ---0.50‡ 700 700 700 700 665
†† 2 --- 1 / 2 --- To n A / C C o o l i n g 875 0 ---0.50‡ 870 870 865 865 865
†† 3 --- To n A / C C o o l i n g 1050 0---0.50‡ 1010 1030 1050 1050 1050
3 --- 1 / 2 --- To n A / C C o o l i n g 1225 0 ---1.0‡ 1155 1180 1200 1210 1220 1225 1225 1225 1225 1225
4 --- To n A / C C o o l i n g 1400 0 ---1.0‡ 1395 1400 1400 1400 1400 1400 1400 1390 1375 1355
5 --- To n A / C C o o l i n g 1750 0 ---1.0‡ 1740 1750 1750 1750 1735 1740 1735 1730 1715 1700
6 --- To n A / C C o o l i n g 2100 0 --- 1 . 0 2075 2085 2090 2100 2100 2100 2090 2080 2055 2025
Maximum 2200 0 --- 1 . 0 2180 2195 2200 2200 2200 2200 2185 2165 2140 2095
155---22
Low Heat 1715 (1440)† 0 --- 1 . 0 1715 1715 1715 1715 1715 1705 1710 1705 1705 1695
High Heat 1970 (1775) 0 --- 1 . 0 1955 1965 1965 1970 1970 1970 1970 1970 1970 1960
†† 2 --- To n A / C C o o l i n g 700 0 ---0.50‡ 700 700 700 700 680
†† 2 --- 1 / 2 --- To n A / C C o o l i n g 875 0 ---0.50‡ 865 875 875 865 865
†† 3 --- To n A / C C o o l i n g 1050 0---0.50‡ 1015 1020 1035 1045 1050
3 --- 1 / 2 --- To n A / C C o o l i n g 1225 0 ---1.0‡ 1160 1185 1215 1225 1225 1225 1225 1225 1225 1225
4 --- To n A / C C o o l i n g 1400 0 ---1.0‡ 1385 1400 1400 1400 1400 1400 1395 1395 1380 1360
5 --- To n A / C C o o l i n g 1750 0 ---1.0‡ 1745 1750 1750 1750 1745 1740 1745 1745 1740 1735
6 --- To n A / C C o o l i n g 2100 0 --- 1 . 0 2055 2070 2080 2085 2095 2100 2100 2100 2090 2065
Maximum 2200 0 --- 1 . 0 2175 2190 2200 2200 2200 2200 2200 2200 2180 2160
*Actual external static pressure (ESP) can be determined by using the fan laws (CFM 2 proportional to ESP); such as, a system with 1180 CFM
at 0.5 ESP would operate at cooling airflow of 1050 CFM at 0.4 ESP and low--- heating airflow of 735 CFM at 0.19 ESP.
{Comfort airflow values are shown in parenthesis. Comfort airflow is selected when the low --- heat rise adjustment switch (SW1 --- 3) is OFF and
the comfort/efficiency switch (SW1--- 4) is ON.
}Ductwork must be sized for high --- heating CFM within the operational range of ESP.
**Wattage data provided is for the circulating blower with bottom return and does not include draft inducer, accessories, or gas controls.
{{Operation within the blank areas of the chart is not recommended because high---heat operation will be above 1.0 ESP.
***All airflows on 110 size furnace are 5% less on side return only installations.