APPENDIX B — CCN POINT TABLE (cont)
See Legend on page 307.
Service\SERVICE1 (cont)
DESCRIPTION VALUE UNITS POINT NAME
TRANSLATOR
ACCESSIBLE
NETWORK
ACCESS
Send comp. drive config? No/Yes cdrv_cfg N N/A
Evap Heater Delta Spt Range: 0 to 6
Default: 2
heatersp N N/A
Freeze Override Offset Range: 0 to 5.8
Default: 0
°F (°C) freez_ov N N/A
Auto Start When SM Lost Disable/Enable auto_sm N N/A
VI Self-Test Threshold Range: 0.5 to 15
Default: 1.15
kW ViPwrChk N N/A
VI Self-Test Enable Off/On ViChkEn N N/A
Pump Rot. AntiFrz Protec Off/On AntiFrz N N/A
HTTP Server Disable/Enable http_en N N/A
FTP Server Disable/Enable ftp_en N N/A
Oil Delta Trigger Speed Range: 0 to 15
Default: 5
Hz odtrspd N N/A
Oil Trigger Time Range: 1800 to 7200
Default: 3600
sec otrigtim N N/A
Oil Delta Recover Speed Range: 0 to 15
Default: 5
Hz odrecspd N N/A
Oil Recover Time Range: 30 to 120
Default: 60
sec orectim N N/A
Water Temp Hysteresis
0.9 to 10
Default: 0.9
V wateesys N N/A
High VI Time at Start
0 to 3600
Default: 900
TONS/H vistrtdt N N/A
Enable High VI at Start
NO_YES TONS/H vistrten N N/A
Approach Ctrl at Start?
NO_YES A apr_en N N/A
Service\UPDTHOUR
DESCRIPTION VALUE UNITS POINT NAME
TRANSLATOR
ACCESSIBLE
NETWORK
ACCESS
Machine Operating Hours hours hr_mach N N/A
Machine Starts Number st_mach N N/A
Compressor A Hours hours hr_cp_a N N/A
Compressor A Starts st_cp_a N N/A
Compressor B Hours hours hr_cp_b N N/A
Compressor B Starts st_cp_b N N/A
Evap Pump #1 Hours hours hr_cpum1 N N/A
Evap Pump #2 Hours hours hr_cpum2 N N/A
VI Cycle Count A Cycles VIctA N N/A
VI Cycle Count B Cycles VIctB N N/A
Circuit A Fan #1 Hours hours hrfana01 N N/A
Circuit A Fan #2 Hours hours hrfana02 N N/A