04701 Loss of Communi-
cation with VLT 
Drive Board #1
Alarm will trip if communication with 
Circuit A Compressor VFD is lost
Circuit A will be shut 
down immediately
Automatic when the commu-
nication is reestablished 
If this condition is encountered, check the fol-
lowing items for faults:
• power supply to the compressor or fan
drive board
• local equipment network (LEN) wiring
• check VFD parameters against list
• check VFD address
• check unit configuration for correct unit
size, low ambient selection, voltage, fre-
quency and tier
04702 Loss of Communi-
cation with VLT 
Drive Board #2
Alarm will trip if communication with 
Circuit B Compressor VFD is lost
Circuit B will be shut 
down immediately
Automatic when the commu-
nication is reestablished 
04704 Loss of Communi-
cation with Fan 
Drive Board #4
Alarm will trip if communication with 
Circuit A Fan A1 VFD is lost
Circuit A will be shut 
down immediately
Automatic when the commu-
nication is reestablished 
04705 Loss of Communi-
cation with Fan 
Drive Board #5
Alarm will trip if communication with 
Circuit A Fan A2 VFD is lost
Circuit A will be shut 
down immediately
Automatic when the commu-
nication is reestablished 
04707 Loss of Communi-
cation with Fan 
Drive Board #7
Alarm will trip if communication with 
Circuit B Fan B1 VFD is lost
Circuit B will be shut 
down immediately
Automatic when the commu-
nication is reestablished 
04708 Loss of Communi-
cation with Fan 
Drive Board #8
Alarm will trip if communication with 
Circuit B Fan B2 VFD is lost
Circuit B will be shut 
down immediately
Automatic when the commu-
nication is reestablished 
04901 Loss of Communi-
cation with SIOB 
Board A
Alarm will trip if communication with 
SIOB-A Board is lost
Unit will be stopped 
immediately
Automatic when the commu-
nication is reestablished 
If this condition is encountered, check the fol-
lowing items for faults:
• power supply to the SIOB
• local equipment network (LEN) wiring
• confirm unit configuration
• check board addressing DIP switches
04902 Loss of Communi-
cation with SIOB 
Board B
Alarm will trip if communication with 
SIOB-B Board is lost
Circuit B will be shut 
down immediately
Automatic when the commu-
nication is reestablished 
55001 Database module 
failure
Tested when the unit is ON or OFF.
If database module returns an error 
alarm will be tripped 
Unit will be stopped Automatic Software malfunction. Power cycle the display.
56001 Lenscan module 
failure
Tested when the unit is ON or OFF.
If lenscan module returns an error 
alarm will be tripped 
Unit will be stopped Automatic Software malfunction. Power cycle the display.
57020 Main EXV step-
per motor failure - 
Circuit A
Criteria For Trip
Tested when unit is ON or OFF. If the 
SIOB detects an EXV motor is not in 
the commanded position, the alarm is 
set
Circuit A shall be 
stopped
Manual • Check EXV connections on SIOB
• Check connection on EXV
57021 Main EXV step-
per motor failure - 
Circuit B
Criteria For Trip
Tested when unit is ON or OFF. If the 
SIOB detects an EXV motor is not in 
the commanded position, the alarm is 
set
Circuit B shall be 
stopped
Manual • Check EXV connections on SIOB
• Check connection on EXV
57023 Main ECO step-
per motor failure - 
Circuit A
Criteria For Trip
Tested when unit is ON or OFF. If the 
SIOB detects an ECO EXV motor is 
not in the commanded position, the 
alarm is set
Circuit A shall be 
stopped
Manual • Check ECO EXV connections on SIOB
• Check connection on ECO EXV
57024 Main ECO step-
per motor failure - 
Circuit B
Criteria For Trip
Tested when unit is ON or OFF. If the 
SIOB detects an ECO EXV motor is 
not in the commanded position, the 
alarm is set
Circuit B shall be 
stopped
Manual • Check ECO EXV connections on SIOB
• Check connection on ECO EXV
60001 VI Solenoid Diag-
nostic Test Failure 
- Circuit A
Tested when unit is ON.VI is cycled from 
ON to OFF and VFD power is measured. 
If power delta between ON/OFF of the VI 
solenoid does not exceed the value in 
SERVICE1_VIPwrChk then this alarm is 
set.
Alert Only Manual • Check VI solenoid for proper operation
61001 VI Solenoid Diag-
nostic Test Failure 
- Circuit B
Tested when unit is ON.VI is cycled from 
ON to OFF and VFD power is measured. 
If power delta between ON/OFF of the VI 
solenoid does not exceed the value in 
SERVICE1_VIPwrChk then this alarm is 
set.
Alert Only Manual • Check VI solenoid for proper operation
07001 Illegal configura-
tion
The alarm will be generated if one of 
these conditions is met:
1. Unit Capacity (Main Menu 
 Config-
uration Menu 
 Factory Parame-
ters) is set to 0 or something other 
than 140, 160, 180, 200, 225, 250, 
275, 300, 325, 350, 400, 450, or 500.
2. Power Supply Voltage (Main Menu 
 Configuration Menu 
 Factory 
Parameters) is set to something 
other than 200, 208/230, 380, 400, 
415, 440, 460, or 575.
3. Low Ambient Option (STD) (Main 
Menu 
 Configuration Menu 
 
Factory Parameters) is 1 (YES) on 
a mid or high tier unit (10th position 
of model number is “M” or “H”).
4. Low Ambient Option (STD) (Main 
Menu 
 Configuration Menu 
 
Factory Parameters) is 1 (YES) on 
a 30XV140 standard tier unit (10th 
position of model number is “S”).
5. DX Evaporator Installed (Main 
Menu 
 Configuration Menu 
 
Factory Parameters) is 1 (YES) for 
30XV350, 30XV400, 30XV450, or 
30XV500.
Unit is not allowed to 
start
Automatic when config-
ured correctly
If this condition is encountered, confirm unit 
configuration
Table 168 — Alarm Details by Code (cont)
ALARM
CODE
ALARM NAME
CRITERIA
FOR TRIP
ACTION TAKEN
BY CONTROL
RESET
METHOD
POSSIBLE CAUSES/CORRECTIVE ACTIONS