25
Machine Control Methods
This  term  refers  to  how  the  machine  is  started  and  stopped.
Several Machine Control Methods are available. 
• Local On
• Local Schedule
•Network
•Remote
•Master
The  Carrier  Controller  Start/Stop  button   is  used  to  select
one of the above control types; see Fig. 24. The Carrier Con-
troller Start/Stop button is used to select one of the above con-
trol types. Once the Start/Stop button is touched, and assuming
the unit is not running, the current start method will be indicat-
ed in green; if this is the case, the option to switch to “Local
Off” will also be available. See Fig. 24 for details. In addition,
when the Local control type is selected, this button can be used
to  select  a  particular  functional  mode:  On,  Off,  or  Schedule
mode. If the Start/Stop button is green the unit is running. If the
Start/Stop button is gray the unit is not running. If the button is
flashing green then the unit is preparing to start.
Fig. 24 — Machine Control Methods
See Fig. 25 for Machine Control Methods Local Off.
LOCAL ON
With this mode selected, the unit is under local control and will
be  allowed  to  start.  The  unit  will  ignore  the  Remote  Control
Contacts, as well as the Enable-Off-Remote Switch (SW1) and
any network commands except Emergency Stop, as well as the
Enable-Off-Remote (SW1) input. Use this method if the unit is
to run all the time without direction from a Building Manage-
ment System or network.
Fig. 25 — Machine Control Methods showing Current 
Start Method and Local Off Option
LOCAL SCHEDULE
With this mode selected, the unit is under local control and will
be  allowed  to  start  if  Occupancy  Schedule  1  Configuration
Menu 
 Schedule Menu 
 OCCPC01S indicates the current
time is within an occupied period. Otherwise, the unit will re-
main  off.  See  “DEFINING  OCCUPANCY  SCHEDULE”  on
page 28  for  details  on  configuring  a  local  schedule. The  unit
will  ignore  the  Remote  Control  Contacts,  as  well  as  the  En-
able-Off-Remote  (SW1)  and  any  network  commands  except
Emergency Stop. Use this method if the unit is to run based on
an occupancy schedule without direction from a Building Man-
agement System or network.
NETWORK
With this mode selected, the unit is under CCN control and will
be controlled by CCN commands. The unit will ignore the Re-
mote  Control  Contacts,  as  well  as  the  Enable-Off-Remote
(SW1) input. Use this method if the unit is to run based on a
Building Management System or network. 
REMOTE
With this mode selected, the unit is under remote control and will
be allowed to start if the Enable-Off-Remote Switch (SW1) is in
the Remote position and the Remote Contacts (TB5-9 and -10) are
closed. Alternatively, if the Enable-Off-Remote Switch (SW1) is
in the Enable position, the unit will operate regardless of the Re-
mote  Contact  status  (TB5-9  and  -10),  since  it  will  be  bypassed.
The  unit  will  ignore  any  network  commands  except  Emergency
Stop. Use this method if the unit is to operate the chiller via a con-
tact closure from a Building Management System.
MASTER
With this mode selected, the unit is operating as the Master unit of
a 2-unit Master-Slave Chiller Plant. The Master unit can be started
under Local On, Local Schedule, Network, or Remote. The excep-
tions  noted  for  each  of  the control methods  will still  apply.  Use
this method if the unit is to run as the Master unit.
Table 19 summarizes the available operating types.