EasyManua.ls Logo

Carrier AquaForce B Series - EXV Control

Carrier AquaForce B Series
358 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
273
APPENDIX A — CARRIER CONTROLLER DISPLAY TABLES (cont)
*Depends on the selected language (English by default).
EXV_CTRL — EXV Control
Carrier Controller PATH:
Main Menu  Maintenance Menu
EXV Control
LINE DISPLAYED TEXT* CCN NAME RANGE
DEFAULT
VALUE
UNIT
READ/
WRITE
1 Circuit A
——
——
2 EXV Override Circuit A
ov_exv_a
——RO
3 EXV Position (Pct) A
EXV_A
—%RO
4 EXV Position (Steps) A
EXV_STPA 0 to 10000
——RO
5 Discharge Superheat A
DSH_A
°F (°C) RO
6 Dis. Superheat Setpnt A
dsh_spa
°F (°C) RO
7 Suction Superheat A
SH_A
°F (°C) RO
8 Suct. Superheat Setpnt A
sh_sp_a
°F (°C) RO
9 Evap ExchangeDT Cir A
pinch_a
°F (°C) RO
10 Subcooling Circuit A
subcoola
°F (°C) RO
11 Subcooling Setpoint A
subc_spa
°F (°C) RO
12 EXV State A
exv_sta
——RO
13 EXV Previous State A
exv_lsta
——RO
14 EXV Wished Position A
exvwposa
——RO
15 EXV Mode A
exv_moda Closed(0)/Open(1)
——RO
16 EXV Mode Text A
exv_txta Closed(0)/Open(1)
——RO
17 Circuit B
——
——
18 EXV Override Circuit B
ov_exv_b
——RO
19 EXV Position (Pct) B
EXV_B
—%RO
20 EXV Position (Steps) B
EXV_STPB 0 to 10000
——RO
21 Discharge Superheat B
DSH_B
°F (°C) RO
22 Dis. Superheat Setpnt B
dsh_spb
°F (°C) RO
23 Suction Superheat B
SH_B
°F (°C) RO
24 Suct. Superheat Setpnt B
sh_sp_b
°F (°C) RO
25 Evap ExchangeDT Cir B
pinch_b
°F (°C) RO
26 Subcooling Circuit B
subcoolb
°F (°C) RO
27 Subcooling Setpoint B
subc_spb
°F (°C) RO
28 EXV State B
exv_stb
——RO
29 EXV Previous State B
exv_lstb
——RO
30 EXV Wished Position B
exvwposb
——RO
31 EXV Mode B
exv_modb Closed(0)/Open(1)
——RO
32 EXV Mode Text B
exv_txtb Closed(0)/Open(1)
——RO
LEGEND
RO Read Only
RW Read/Write
Spt Set Point

Table of Contents