APPENDIX A — CARRIER CONTROLLER DISPLAY TABLES (cont)
*Depends on the selected language (English by default).
MST_SLV — Master/Slave Configuration
Carrier Controller PATH:
Main Menu Configuration Menu
Master/Slave Configuration
LINE DISPLAYED TEXT* CCN NAME RANGE
DEFAULT
VALUE
UNIT
READ/
WRITE
1
Master/Slave Select
ms_sel 0 to 2
Disable(0) — RW
0=Disable
1=Master
2=Slave
2
Master Control Type
ms_ctrl 1 to 3
Local Con-
trol(1)
—RW
1=Local Control
2=Remote Control
3=CCN Control
3 Slave Address
slv_addr 1 to 236
2—RW
4
Lead/Lag Select
lead_sel 0 to 2
0—RW
0=Always Lead
1=Lag Once Failed Only
2= Lead/Lag Runtime Sel
5 Lead/Lag Balance Delta
ll_bal_d 40 to 400
168 Hours RW
6 Lead Lag Start Timer
lstr_tim 2 to 30
10 min RW
7 Lead Pulldown Time
lead_pul 0 to 60
0minRW
8 Start of Error Higher
start_dt
3 to 18(-16.1 to -
7.8)
4(-15.6) °F(°C) RW
9 Lag Minimum Running Time
lag_mini 0 to 150
0minRW
10
Lag Unit Pump Control
lag_pump 0 to 1
0—RW0=Stop if Unit Stops
1=Run if Unit Stops
11 Chiller in Series
ll_serie No(0)/Yes(1)
No(0) — RW
CP_ENABL — Compressor Enable
Carrier Controller PATH:
Main Menu Configuration Menu
Compressor Enable
LINE DISPLAYED TEXT* CCN NAME RANGE
DEFAULT
VALUE
UNIT
READ/
WRITE
1 DISABLE COMPRESSORS
2 Compressor A Disable
en_cp_a No(0)/Yes(1)
No(0) — RW
3 Compressor B Disable
en_cp_b No(0)/Yes(1)
No(0) — RW
LEGEND
RW — Read/Write
Spt — Set Point