307
APPENDIX B — CCN POINT TABLE (cont)
LEGEND
Service\UPDTHOUR (cont)
DESCRIPTION VALUE UNITS POINT NAME
TRANSLATOR
ACCESSIBLE
NETWORK
ACCESS
Circuit A Fan #3 Hours hours hrfana03 N N/A
Circuit A Fan #4 Hours hours hrfana04 N N/A
Circuit A Fan #5 Hours hours hrfana05 N N/A
Circuit A Fan #6 Hours hours hrfana06 N N/A
Circuit A Fan #7 Hours hours hrfana07 N N/A
Circuit A Fan #8 Hours hours hrfana08 N N/A
Circuit A Fan #9 Hours hours hrfana09 N N/A
Circuit A Fan #10 Hours hours hrfana10 N N/A
Circuit A Fan #11 Hours hours hrfana11 N N/A
Circuit A Fan #12 Hours hours hrfana12 N N/A
Circuit A Fan #13 Hours hours hrfana13 N N/A
Circuit A Fan #14 Hours hours hrfana14 N N/A
Circuit B Fan #1 Hours hours hrfanb01 N N/A
Circuit B Fan #2 Hours hours hrfanb02 N N/A
Circuit B Fan #3 Hours hours hrfanb03 N N/A
Circuit B Fan #4 Hours hours hrfanb04 N N/A
Circuit B Fan #5 Hours hours hrfanb05 N N/A
Circuit B Fan #6 Hours hours hrfanb06 N N/A
Circuit B Fan #7 Hours hours hrfanb07 N N/A
Circuit B Fan #8 Hours hours hrfanb08 N N/A
Circuit B Fan #9 Hours hours hrfanb09 N N/A
Circuit B Fan #10 Hours hours hrfanb10 N N/A
Circuit B Fan #11 Hours hours hrfanb11 N N/A
Circuit B Fan #12 Hours hours hrfanb12 N N/A
Circuit B Fan #13 Hours hours hrfanb13 N N/A
Circuit B Fan #14 Hours hours hrfanb14 N N/A
Setpoint\SETPOINT
DESCRIPTION VALUE UNITS POINT NAME
TRANSLATOR
ACCESSIBLE
NETWORK
ACCESS
Cooling Setpoint 1 Range: –20 to 78.8 (–28.9 to 26)
Default: 44
°F (°C) csp1 N N/A
Cooling Setpoint 2 Range: –20 to 78.8 (–28.9 to 26)
Default: 44
°F (°C) csp2 N N/A
Cooling Ice Setpoint Range: –20 to 78.8 (–28.9 to 26)
Default: 44
°F (°C) ice_sp N N/A
Cooling Ramp Loading Range: 0.2 to 20
Default: 1
°F (°C) cramp_sp N N/A
Switch Limit Setpoint 1 Range: 0 to 100
Default: 100
% lim_sp1 N N/A
Switch Limit Setpoint 2 Range: 0 to 100
Default: 100
% lim_sp2 N N/A
Switch Limit Setpoint 3 Range: 0 to 100
Default: 100
% lim_sp3 N N/A
RO — Read Only
RW — Read/Write