57
12.2.5 - Brine option (Options 5B and 6B)
The 5B medium-temperature brine solution option is used to
produce low temperature chilled water down to 0°C.
Brine production from 0°C to -15°C is only possible with the
low-temperature brine solution option (6B).
The unit is equipped with insulation on the suction pipes. The
insulation is reinforced on the low-temperature brine solution
option.
The operating range depends on:
• the size of the unit,
• the glycol type,
• its concentration,
• the ow rate,
• the temperature of the glycol solution,
• the condensation pressure (ambient temperature).
Operating range
• Low-temperature brine solution
Brinesolutionwatertypeheatexchangerwateroutlettemperature(°C)
• Medium-temperature brine solution
Brinesolutionwatertypeheatexchangerwateroutlettemperature(°C)
Inletairtemperature(°C)
Brinesolutionwatertypeheatexchangerwateroutlettemperature(°C)
- EvaporatorΔT=3K
- These operatingrangesare guidelinesonly.Verify the operatingrangewith the
Carrierelectroniccatalogue.
Key
30RBM or 30RBP brine operating range
Operating range for 30RBM unit equipped with options 28B and 28C (winter
operation).Options28B-28C(withtwo-speedleadfanforeachcircuit)allows
operationdownto-10°Coutsidetemperature.
RBP operating range or extension of the operating range, 30RBM unit
equippedwithoption28forthemedium-temperaturebrinesolutionoption.
Option 28 (with variable-speed lead fan for each circuit) allows operation
downto-20°Coutsidetemperature.
Partloadoperatingrangeforthemedium-andlow-temperatureoptions.
Inletairtemperature(°C)Inletairtemperature(°C)
RBP
RBM Options 28B-28C
Options 28B-28C for size RBM 160
RBP
Options 28B-28C for RBM
Options 28B-28C for size RBM 160
Options 28B-28C for RBM
Options 28B-28C for size RBM 160
RBP or Option 28 for RBM