30RQ-RQP 165R 180R 210R 230R 270R 310R 330R 370R 400R 430R
Rated short-circuit
withstand currents
Rated short time (1s) 
current - Icw
(Module 1/Module 2)
(a)
kA e󰀨 5,5 8,5 8,5 8,5 8,5 20 20 20 20 20
Rated peak current - Ipk
(Module 1/Module 2)
(a)
kA pk 154 330 330 330 330 330 330 330 330 330
Value with upstream electrical
protection
(1)
Rated conditional short
circuit current Icc
(Module 1/Module 2)
(a)
kA e󰀨 50 50 50 50 50 50 50 50 50 50
Associated protection - type
(Module 1/Module 2)
(a)
INS250 INS250 INS250 INS250 INS250 INS400 INS400 INS400 INS400 INS400
Associated protection
(rating/reference)
Module 1
(a)
TM160D /
LV430840
TM200D /
LV431831
TM250D /
LV431831
TM250D /
LV431831
TM250D /
LV431831
Micrologic
2,3 400 A /
LV432693
Micrologic
2,3 400 A /
LV432693
Micrologic
2,3 400 A /
LV432693
Micrologic
2,3 400 A /
LV432693
Micrologic
2,3 400 A /
LV432693
Module 2
(a)
- - - - - - - - - -
30RQ-RQP 470R 520R 620R 660R 740R 800R 860R 940R 1040R
Rated short-circuit
withstand currents
Rated short time (1s) 
current - Icw
(Module 1/Module 2)
(a)
kA e󰀨 20 20 20 / 20 20 / 20 20 / 20 20 / 20 20 / 20 20 / 20 20 / 20
Rated peak current - Ipk
(Module 1/Module 2)
(a)
kA pk 330 330 330 / 330 330 / 330 330 / 330 330 / 330 330 / 330 330 / 330 330 / 330
Value with upstream electrical
protection
(1)
Rated conditional short
circuit current Icc
(Module 1/Module 2)
(a)
kA e󰀨 50 50 50 / 50 50 / 50 50 / 50 50 / 50 50 / 50 50 / 50 50 / 50
Associated protection - type
(Module 1/Module 2)
(a)
INS500 INS500
INS400 /
INS400
INS400 /
INS400
INS400 /
INS400
INS400 /
INS400
INS400 /
INS400
INS500 /
INS500
INS500 /
INS500
Associated protection
(rating/reference)
Module
1
(a)
Micrologic
2,3 630 A /
LV432893
Micrologic
2,3 630 A /
LV432893
Micrologic
2,3 400 A /
LV432693
Micrologic
2,3 400 A /
LV432693
Micrologic
2,3 400 A /
LV432693
Micrologic
2,3 400 A /
LV432693
Micrologic
2,3 400 A /
LV432693
Micrologic
2,3 630 A /
LV432893
Micrologic
2,3 630 A /
LV432893
Module
2
(a)
- -
Micrologic
2,3 400 A /
LV432693
Micrologic
2,3 400 A /
LV432693
Micrologic
2,3 400 A /
LV432693
Micrologic
2,3 400 A /
LV432693
Micrologic
2,3 400 A /
LV432693
Micrologic
2,3 630 A /
LV432893
Micrologic
2,3 630 A /
LV432893
(1)  If  another  current  limitation  protection  device  is  used,  its  time-current  and  thermal  constraint  (I²t)  trip  characteristics  must  be  at  least  equivalent  to  those  of  the 
recommended protection.
(a)  Modules 1 and 2 only relate to sizes 620R to 1040R.
Note: The short-circuit withstand current capability values above have been established for the TN system.
IT system: The short circuit holding current values given above for the TN system are not valid for IT; modications are
required.
5 - PHYSICAL AND ELECTRICAL DATA FOR THE UNITS
23