Do you have a question about the Carrier ComfortLink 30GXN and is the answer not in the manual?
Refrigerant | R-134a |
---|---|
Compressor Type | Screw |
Control System | ComfortLink |
Efficiency | High |
Sound Power Level | 80-85 dBA (typical, varies by model) |
Operating Voltage Range | 380-480V, 3-phase, 50/60 Hz |
Dimensions (L x W x H) | Varies significantly by model (Consult specific model data) |
Electrical shock can cause personal injury and death. Shut off all power.
Do not use jumpers or short components; may destroy modules.
Run fluid through heat exchangers when adding/removing refrigerant charge.
Vent relief valves outdoors per ANSI/ASHRAE 15.
Controls refrigerant flow via stepper motor for precise cooler level control.
Prelubricates compressor and maintains oil pressure during operation.
Fan staging controlled by SCT or Head Pressure Set Point.
Optional controller for low-ambient operation using temperature sensor.
Lists conditions causing total unit stoppage, including safety trips and power failures.
Lists conditions causing stoppage of only one circuit, like low oil pressure.
Steps for restarting after stoppage, noting manual reset requirements.
Warnings of abnormal conditions causing unit shutdown or default value usage.
Steps for physical inspection and opening of EXV valves, including O-ring replacement.
Procedures for tube plugging, retubing, and tightening head bolts.
Guidelines for cleaning cooler tubes and inspecting sensors for corrosion.
How to check for low refrigerant charge using sight glass and EXV percent open.
Procedure for adding refrigerant charge to 30HXC units.
Procedure for adding refrigerant charge to 30GX and 30HXA systems.
Step-by-step procedure for changing a compressor, including tool requirements.
Procedures for replacing thermistors T1-T6 and motor thermistors.
Details on module operation, LEDs, communication, and troubleshooting.
Guidelines for routine, monthly, and yearly maintenance tasks.
Ensures all auxiliary components and accessories are installed and wired correctly.
Procedure for actual chiller start-up and verifying proper operation.
Configuration header punch-outs and must trip amps for 30GXN,R high ambient models.
Configuration header punch-outs and must trip amps for 30GXN,R reduced ambient models.
Configuration header punch-outs and must trip amps for 30HXC models.
Configuration header punch-outs and must trip amps for 30HXA models.
Configuration settings for PID gains, motor temperature, and compressor enable.
Enables testing of peripheral components before compressor start-up.