ComfortVu™ BACnet Thermostat Model Standard TB-HM (Line voltage)Carrier Proprietary and Confidential CARRIER CORPORATION ©2020
Installation and Operation Guide All rights reserved
45
Technician Settings P11 to P15
P11 Window contact delay time
Range: 0…999 seconds.
Default: 600 seconds.
P12 Door switch (terminals T1,0) polarity
“01” - Normally open
“00” - Normally closed
P13 Door switch delay time
Range: 0…999 seconds.
Default: 180 seconds.
P14 Enable/Disable Auto change over mode
“00” - Disable Auto change over mode
“01” - Enable Auto change over mode
P15 Motion sensor logic (PIR)
“00” - Thermostat turns off when unoccupied and back on
when re-occupied.
“01” - Thermostat turns off when unoccupied and remains
off when re-occupied.
“02” - Thermostat uses economy setpoints when
unoccupied.