ComfortVu™ BACnet Thermostat Model Standard TB-HM (Line voltage)Carrier Proprietary and Confidential CARRIER CORPORATION ©2020
Installation and Operation Guide All rights reserved
50
Technician Settings P43 to P44
P43 P44
Soft start in heat
with fan on demand (auto fan) active.
P43 Soft start in heat cut-in temperature (FC only)
The fan will not start before the temperature on T3 sensor reaches the
cut-in temperature.
See Technician Settings P08/P09.
Range: 14...37°C / 57…99°F
Default: 36°C / 97°F
P44 Soft start in heat cut-out temperature (FC only)
The fan will stop if the temperature on T3 sensor drops below the cut-out
temperature.
See Technician Settings P08/P09.
Range: 12...35°C / 54…95°F
Default: 32°C / 90°F