ERROR AND STATUS CODES
6
5
For the following three tables, the indicator light mentioned in the rst
column is the green LED on the front cover, under the power switch.
Indicator Light Code Explanation Possible Cause Recommended Action
OFF
No incoming
AC power to air
purier control
electronics
Normal operation when airow is
not present for models without ow
sensor due to AC power to purier
being off at furnace control board
(EAC terminals)
ON/OFF power switch
turned to OFF
Turn purier power switch
to ON position
Power to entire system is off
(furnace and air purier)
Check that the HVAC system
is switched on
Blown fuse or tripped circuit
breaker for HVAC system
Replace fuse or reset circuit
breaker, call for service if
problem reoccurs
Misaligned or damaged
purier door
Insure that door is undamaged
and properly installed on
purier cabinet
Damaged or disconnected
incoming power wiring
Call for service
ON (continuously) Air purier on
Normal operation when
airow is present
Flashing
(one ash every
four seconds)
Standby mode
Normal operation when airow
is not present for models with
ow sensor
Ions detected in airow
due to missing replaceable
lter element
Place lter in air purier
Debris is covering airow sensor
(for models including an
airow sensor)
Make sure ow sensor is
clean and unobstructed
Flow sensor is damaged
(for models including an
airow sensor)
Replace ow sensor,
available as replacement kit
(KIT160000)
Flow sensor bypass assembly is
damaged (for models without an
airow sensor)
Replace ow sensor bypass
assembly, available as
replacement kit (KIT161000)
One or more of the three airow
sensor contact springs on purier
cabinet downstream rail are bent
of damaged
Replace ow sensor contact
spring assembly, included as part
of the ow sensor kits
(KIT160000) and ow sensor
bypass kit (KIT161000)
Table 1: Operating Status Codes
When the rapid ashing code occurs on the green light, the controls for the high voltage need to be reset.
To reset the controls, the power switch needs to be turned on and off for three cycles.
1. Turn off power by depressing the power switch.
2. Wait approximately two seconds before turning
the power back on.
3. Wait approximately two seconds before turning
the power off.
4. Repeat Steps 2 and 3 for two more on/off cycles.
5. After the three on/off cycles are completed, turn
on power by depressing the power switch on. The
rapid ashing code on the green light should no
longer be displayed. If the rapid ashing code on
the green light is still displayed, repeat Steps 1
through 5.
Note: By resetting the air purier controls the issue
with air purier will need to be addressed by
cleaning or servicing the air purier.
Reset Procedure