29
Table 6A — Unit Electrical Data, 30HXC Units (cont)
LEGEND
NOTES:
1. Each main power source must be supplied from a field-supplied fused
electrical service with a (factory-installed or field-installed) disconnect
located in sight from the unit.
2. Control circuit power must be supplied from a separate source
through a field-supplied disconnect (except for 380/415-50 units). An
accessory control transformer may be used to provide control circuit
power from the main unit power supply.
3. Maximum incoming wire size for each terminal block is 500 kcmil.
4. Maximum allowable phase imbalance is: voltage, 2%; amps, 5%.
5. Use copper conductors only.
6. The MOCP is calculated as follows:
MOCP = (2.25) (largest RLA) + the sum of the other RLAs. Size the
fuse one size down from the result. The RLAs are listed on the name-
plate.
The recommended fuse size in amps (RFA) is calculated as follows:
RFA = (1.50) (largest RLA) + the sum of the other RLAs. Size the fuse
one size up from the result. The RLAs are listed on the nameplate.
UNIT
30HXC
UNIT VOLTAGE
POWER
SUPPLY
QTY. REQD.
NO. POWER
SUPPLY
CONDUCTORS
UNIT VOLTAGE CONTROL CIRCUIT
V-Hz
(3 Ph)
Supplied
MCA MOCP
ICF Rec Fuse Size V-Hz
(Single
Ph)
Supplied MCA
and
MOCP
Min Max XL WD XL WD Min Max
161
230-60 207 253 1 6 398.7 600 — 574.8 — 500 115-60 104 127 15
208/230-60 187 253 1 6 443.0 600 — 590.6 — 600 115-60 104 127 15
460-60 414 506 1 3 200.1 300 756.2 287.2 250 250 115-60 104 127 15
575-60 518 633 1 3 159.9 225 604.9 229.9 200 200 115-60 104 127 15
380-60 342 418 1 3 242.2 350 843.2 325.2 300 300 230-60 207 254 15
380/415-50 342 440 1 3 249.0 350 944.2 358.2 300 300 230-50 198 254 15
230-50 207 253 1 6 411.3 600 — 577.7 — 500 230-50 207 254 15
171
230-60 207 253 1 6 428.4 600 — 604.5 — 500 115-60 104 127 15
208/230-60 187 253 1 6 476.0 700 — 623.6 — 600 115-60 104 127 15
460-60 414 506 1 3 215.0 300 771.1 302.1 250 250 115-60 104 127 15
575-60 518 633 1 3 171.8 250 616.8 241.8 200 200 115-60 104 127 15
380-60 342 418 1 3 260.2 350 861.2 343.2 300 300 230-60 207 254 15
380/415-50 342 440 1 3 266.6 350 961.8 375.8 300 300 230-50 198 254 15
230-50 207 253 1 6 440.4 600 — 606.8 — 500 230-50 207 254 15
186
230-60 207 253 1 6 462.3 600 — 638.5 — 600 115-60 104 127 15
208/230-60 187 253 1 6 513.7 700 — 661.3 — 600 115-60 104 127 15
460-60 414 506 1 3 232.0 300 788.1 319.1 300 300 115-60 104 127 15
575-60 518 633 1 3 185.4 250 630.4 255.4 225 225 115-60 104 127 15
380-60 342 418 1 3 280.8 400 881.8 363.8 350 350 230-60 207 254 15
380/415-50 342 440 1 3 289.4 400 984.6 398.6 350 350 230-50 198 254 15
230-50 207 253 1 6 478.1 600 — 644.5 — 600 230-50 207 254 15
206
230-60 207 253 1 6 524.5 700 — 700.7 — 600 115-60 104 127 15
208/230-60 187 253 1 6 582.8 800 — 730.4 — 700 115-60 104 127 15
460-60 414 506 1 3 263.2 350 819.3 350.3 300 300 115-60 104 127 15
575-60 518 633 1 3 210.4 250 655.4 280.4 250 250 115-60 104 127 15
380-60 342 418 1 3 318.6 400 919.6 401.6 350 350 230-60 207 254 15
380/415-50 342 440 1 3 326.8 450 1022.0 436.0 400 400 230-50 198 254 15
230-50 207 253 1 6 539.8 700 — 706.2 — 600 230-50 207 254 15
246
230-60 207 253 1 6 604.1 800 — 780.3 — 700 115-60 104 127 15
208/230-60 187 253 1 6 671.3 800 — 818.9 — 800 115-60 104 127 15
460-60 414 506 1 3 303.2 400 859.3 390.3 350 350 115-60 104 127 15
575-60 518 633 1 3 242.3 300 687.3 312.3 300 300 115-60 104 127 15
380-60 342 418 1 3 367.0 450 968.0 450.0 400 400 230-60 207 254 15
380/415-50 342 440 1 3 377.6 500 1072.8 486.8 450 450 230-50 198 254 15
230-50 207 253 1 6 623.8 800 — 790.2 — 700 230-50 207 254 15
261
230-60 207 253 1 6 633.8 800 — 810.0 — 700 115-60 104 127 15
208/230-60 187 253 1 6 704.3 800 — 851.9 — 800 115-60 104 127 15
460-60 414 506 1 3 318.1 400 874.2 405.2 350 350 115-60 104 127 15
575-60 518 633 1 3 254.2 300 699.2 324.2 300 300 115-60 104 127 15
380-60 342 418 1 6 385.0 500 986.0 468.0 450 450 230-60 207 254 15
380/415-50 342 440 1 6 395.2 500 1090.4 504.4 450 450 230-50 198 254 15
230-50 207 253 1 6 652.9 800 — 819.3 — 800 230-50 207 254 15
271
230-60 207 253 1 6 667.8 800 — 843.9 — 800 115-60 104 127 15
208/230-60 187 253 1 6 742.0 800 — 889.6 — 800 115-60 104 127 15
460-60 414 506 1 3 335.1 400 891.2 422.2 400 400 115-60 104 127 15
575-60 518 633 1 3 267.8 350 712.8 337.8 300 300 115-60 104 127 15
380-60 342 418 1 6 405.6 500 1006.6 488.6 450 450 230-60 207 254 15
380/415-50 342 440 1 6 418.0 500 1113.2 527.2 500 500 230-50 198 254 15
230-50 207 253 1 6 690.6 800 — 857.0 — 800 230-50 207 254 15
ICF — Maximum Instantaneous Current Flow during start-up (the
point in the starting sequence where the sum of the LRA for
the start-up compressor, plus the total RLA for all running
compressors is at a maximum)
LRA — Locked Rotor Amps
MCA — Minimum Circuit Ampacity (for wire sizing)
MOCP — Maximum Overcurrent Protection
RLA — Rated Load Amps
WD — Wye-Delta Start
XL — Across-the-Line Start