Table 7A — Compressor Electrical Data, 30HXC Units (cont)
LEGEND
*Units are shipped with wye-delta start as standard. Across-the-line start is not available.
UNIT SIZE 30HXC
NAMEPLATE
V-Hz
(3 Phase)
COMPRESSOR NUMBERS
A1 B1
RLA LRA RLA LRA
161-XL
208/230-60 * * * *
230-60 * * * *
460-60 103.1 685 71.2 525
575-60 82.4 548 56.9 420
380-60 124.8 757 86.2 580
230-50 * * * *
380/415-50 128.6 856 88.2 600
161-WD
208/230-60 228.8 433 157.6 350
230-60 205.5 433 141.8 350
460-60 103.1 216 71.2 175
575-60 82.4 173 56.9 140
380-60 124.8 239 86.2 193
230-50 212.5 432 145.7 348
380/415-50 128.6 270 88.2 200
171-XL
208/230-60 * * * *
230-60 * * * *
460-60 86.1 580 103.1 685
575-60 68.8 484 82.4 548
380-60 104.2 641 124.8 757
230-50 * * * *
380/415-50 105.8 715 128.6 856
171-WD
208/230-60 190.6 367 228.8 433
230-60 171.5 367 205.5 433
460-60 86.1 183 103.1 216
575-60 68.8 147 82.4 173
380-60 104.2 203 124.8 239
230-50 174.8 361 212.5 432
380/415-50 105.8 233 128.6 270
186-XL
208/230-60 * * * *
230-60 * * * *
460-60 103.1 685 103.1 685
575-60 82.4 548 82.4 548
380-60 124.8 757 124.8 757
230-50 * * * *
380/415-50 128.6 856 128.6 856
186-WD
208/230-60 228.8 433 228.8 433
230-60 205.5 433 205.5 433
460-60 103.1 216 103.1 216
575-60 82.4 173 82.4 173
380-60 124.8 239 124.8 239
230-50 212.5 432 212.5 432
380/415-50 128.6 270 128.6 270
LRA — Locked Rotor Amps
RLA — Rated Load Amps
WD — Wye-Delta Start
XL — Across-the-Line Start