38
Table 7B — Compressor Electrical Data, 30HXA Units (cont)
LEGEND
*Units are shipped with wye-delta start as standard. Across-the-line start is not available.
UNIT SIZE 30HXA
NAMEPLATE
V-Hz
(3 Phase)
COMPRESSOR NUMBERS
A1 B1
RLA LRA RLA LRA
161-XL
208/230-60 * * * *
230-60 * * * *
460-60 157.9 1175 106.6 790
575-60 126.2 940 85.1 630
380-60 191.2 1299 129.0 870
230-50 * * * *
380/415-50 201.2 1265 133.4 1045
161-WD
208/230-60 349.6 743 235.9 527
230-60 314.6 743 212.3 527
460-60 157.9 371 106.6 263
575-60 126.2 297 85.1 211
380-60 191.2 410 129.0 290
230-50 332.3 638 220.3 607
380/415-50 201.2 400 133.4 348
171-XL
208/230-60 * * * *
230-60 * * * *
460-60 129.6 920 157.9 1175
575-60 103.6 736 126.2 940
380-60 156.9 1017 191.2 1299
230-50 * * * *
380/415-50 161.7 1226 201.2 1265
171-WD
208/230-60 286.9 581 349.6 743
230-60 258.2 581 314.6 743
460-60 129.6 291 157.9 371
575-60 103.6 233 126.2 297
380-60 156.9 321 191.2 410
230-50 267.2 619 332.3 638
380/415-50 161.7 387 201.2 400
186-XL
208/230-60 * * * *
230-60 * * * *
460-60 157.9 1175 157.9 1175
575-60 126.2 940 126.2 940
380-60 191.2 1299 191.2 1299
230-50 * * * *
380/415-50 201.2 1265 201.2 1265
186-WD
208/230-60 349.6 743 349.6 743
230-60 314.6 743 314.6 743
460-60 157.9 371 157.9 371
575-60 126.2 297 126.2 297
380-60 191.2 410 191.2 410
230-50 332.3 638 332.3 638
380/415-50 201.2 400 201.2 400
LRA — Locked Rotor Amps
RLA — Rated Load Amps
WD — Wye-Delta Start
XL — Across-the-Line Start