GH7T: Installation Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
2
Installation
Check Equipment and Job Site
IMPORTANT:  All  split  system  and  packaged  heat  pumps  must  be
installed pursuant  to applicable regional efficiency standards issued by
the Department of Energy.
Unpack Unit
Move to final location. Remove carton taking care not to damage unit. 
Inspect Equipment
File  claim  with  shipping  company  prior  to  installation  if  shipment  is
damaged or incomplete. Locate unit rating plate on unit corner panel. It
contains information needed to properly install unit. Check rating plate
to be sure unit matches job specifications.
Install on a Solid, Level Mounting Pad
If conditions or local codes require the unit be attached to pad, tie down
bolts  should  be  used  and fastened  through  knockouts  provided  in  unit
base pan. Refer to unit mounting pattern in Fig. 2 to determine base pan
size and knockout hole location.
For  hurricane  tie  downs,  contact  distributor  for  details  and  PE
Certification (Professional Engineer), if required.
On rooftop  applications,  mount on  level platform  or  frame.  Place unit
above a load-bearing wall and isolate unit and tubing set from structure.
Arrange supporting members to adequately support unit  and  minimize
transmission  of  vibration  to  building.  Consult  local  codes  governing
rooftop applications. 
Roof  mounted  units  exposed  to  winds  above  5  mph  (8.05  km/h)  may
require  wind  baffles.  Consult  the  Service  Manual  -  Residential  Split
System Air Conditioners and Heat Pumps for wind baffle construction.
NOTE:  Unit  must  be  level  to within  ±2°(±3/8  in./ft,±9.5  mm/m.)  per
compressor manufacturer specifications.
Clearance Requirements
When  installing,  allow  sufficient  space  for  airflow  clearance,  wiring,
refrigerant  piping,  and  service. Allow  24  in.  (609.6  mm)  clearance  to
service  end  of  unit  and  48  in.  (1219.2  mm)  (above  unit.  For  proper
airflow, a 6-in. (152.4 mm) clearance on 1 side of unit and 12-in. (304.8
mm) on all remaining sides must be maintained. Maintain a distance of
24 in. (609.6 mm) between units.  Position so water, snow, or ice from
roof or eaves cannot fall directly on unit. 
On rooftop applications, locate unit at least 6 in. (152.4 mm)  above roof
surface.
A05177
Fig. 2 – Tiedown Knockout Locations
Check Defrost Thermostat
Check  defrost  thermostat  to  ensure  it  is  properly  located  and  securely
attached.  There  is  a  liquid  header  with  a  distributor  and  feeder  tube
going into outdoor coil. At the end of the one of the feeder tubes, there is
a  3/8  in.  O.D.  stub  tube  approximately  2  in.  long.  (See  Fig. 3.)  The
defrost thermostat should be located on stub tube. Note that there is only
one stub tube used with liquid header, and on most units it is the bottom
circuit. 
A97517
Fig. 3 – Defrost Thermostat Location
Elevate Unit
Elevate  unit  per  local  climate  and  code  requirements  to  provide
clearance above estimated snowfall level and ensure adequate drainage
of unit. 
CAUTION
!
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet  metal  parts  may  have sharp edges or burrs. Use care and wear
appropriate protective clothing and gloves when handling parts.
CAUTION
!
UNIT OPERATION HAZARD
Failure  to  follow  this  caution  may  result  in  equipment  damage  or
improper operation.
Locate  the  unit  in  such  a  way  that  it  is  stable  in  all  circumstances
including adverse weather conditions. 
UNIT BASE PAN
Dimension in. 
(mm)
TIEDOWN KNOCKOUT LOCATIONS in. (mm)
A B C
35 X 35
(889 X 889)
9–1/8 (231.8) 6–9/16 (166.7) 28–7/16 (722.3)
CAUTION
!
UNIT OPERATION HAZARD
Failure  to  follow  this  caution  may  result  in  equipment  damage  or
improper operation.
Do not allow water and/or ice to build up in base pan.
FEEDER TUBE
DEFROST
THERMOSTAT
A97517
STUB TUBE
COIL