GH7T: Installation Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
6
A12258
Fig. 9 – Thermidistat Wiring with Fan Coil
and 2-Stage Heat Pump
A12259
Fig. 10 – Thermidistat with Variable Speed Furnace 
and 2--Stage Heat Pump
A09306
Final Wiring Check
IMPORTANT:  Check  factory  wiring  and  field  wire  connections    to
ensure terminations are secured properly. Check wire routing to ensure
wires are not in contact with tubing, sheet metal, etc.
Compressor Crankcase Heater
All sizes are equipped with a crankcase heater. Furnish power to heater a
minimum  of  24  hours before  starting  unit. To furnish  power  to  heater
only,  set  thermostat  to OFF  and  close  electrical  disconnect  to  outdoor
unit. 
A crankcase heater is required if refrigerant tubing is longer than 80 ft.
(24.4 m), or when outdoor unit is 20 ft. (6.1 m) below the indoor unit.
Refer to the Residential Piping and Long Line Guideline.
Install Electrical Accessories
Refer  to  the  individual  instructions  packaged  with  kits  or  accessories
when installing.
Airflow Selections (ECM Furnaces)
The ECM Furnaces provide blower operation to match the capacities of
the  compressor  during  high  and  low  stage  cooling  operation.  Tap
selections on the furnace control board enable the installing technician to
select  the  proper  airflows  for  each  stage  of  cooling.  Below  is  a  brief
summary of the furnace airflow configurations
1. The Y2 call for high stage cooling energizes the “Cool” tap on the
control board. The grey wire from cool tap is connected to tap 5 on
the  motor.  Refer  to  the  furnace  Product  Data  to  find  the
corresponding airflow. If the airflow setting for high cooling needs
to be switched from tap 5 to a different tap, jumper a connection
from  the  cool  tap  to  the  desired  tap  so  that  the  Y2  signal  is
communicated via the cool tap to the desired speed tap.
2. The Y1  call for  low stage cooling energizes the “Fan” tap  on the
control board. The red wire from the fan tap is connected to tap 1 on
the  motor.  Refer  to  the  furnace  Product  Data  to  find  the
corresponding airflow. If the airflow setting for low cooling needs
to  be  switched from tap 1  to  a  different tap, jumper a  connection
from  the  Fan    tap  to  the  desired  tap  so  that  the  Y1  signal  is
communicated  via  the  Fan  tap  to  the  desired  speed  tap.  The Y1
setting will also govern the continuous fan airflow for the furnace.
Refer to the literature for the furnace for further details.
Airflow Selection for Variable Speed Furnaces 
(non-communicating)
The  variable  speed  furnaces  provide  blower  operation  to  match  the
capacities  of  the  compressor  during  high  and  low  stage  cooling
operation. The furnace control board allows the installing technician to
select the proper airflows for each stage of cooling. Below is a summary
of  required  adjustments.  See  furnace  installation  instructions  for  more
details: 
1. Turn SW1-5 ON for 400 CFM/ton airflow or OFF for 350 CFM/ton
airflow.  Factory default is OFF.
2. The A/C  DIP switch  setting determines  airflow  during  high  stage
cooling operation. Select the A/C DIP switch setting corresponding
to  the  available  airflow  shown  in  the  furnace  Installation
Instructions that most closely matches the required airflow shown
in the air conditioning Product Data for HIGH speed.
3. The  CF  DIP  switch  setting  determines  airflow  during  low  stage
cooling operation. Select the CF DIP switch setting corresponding
to  the  available  airflow  shown  in  the  furnace  installation
instructions that most closely matches the required airflow shown
in the air conditioning Product Data for LOW speed. If a higher or
lower continuous fan speed is desired, the continuous fan speed can
be  changed  using  the  fan  switch  on  the  thermostat.  Refer  to  the
furnace  Installation  Instructions  for  details  of  how  to  use  this
feature.