SYSTEM OPERATING E NVELOPE
53MVC/MVQ System Operating Envelope Chart
40
50
60
70
80
90
100
110
120
-10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140
Outdoor Temperature (ºF)
Indoor Temperature (ºF)
0
5
10
15
20
25
30
35
40
45
50
55
60
-40-35-30-25-20-15-10-5 0 5 1015202530354045505560
Outdoor Temperature (ºC)
Indoor Temperature (ºC)
Cooling
Continuous
Operation
Heating
Continuous
Operation
85º
F
55º
75ºF
55ºF
5ºF
80ºF
125º
Use low ambient control if the unit will operate in cooling at ambient conditions below 55_F (12.78_C).
A08180
Fig. 4 System Operating Enevelope
ELECTRICAL DATA
UNIT
SIZE
OPERATING
VOLTAGE*
COMPRESSOR OUTDOOR FAN INDOOR FAN
MCA
MAX
FUSE/CB
AMP
MAX/MIN V O L T S --- P H --- H Z RLA LRA FLA HP W VOLTS FLA HP W
009
127/104 1 1 5 --- 1 --- 6 0
7.5 40
0.60 0.102 23 35 DC
1.1 0.034 20 12 20
012 9.9 47 1.18 0.044 25 15 25
012
253/187 208/230---1---60
5.2 21 0.38 0.116 36 35 DC 1.18 0.044 25 9 15
018 7.3 32.6 0.78 0.224 53
208/230---1---60
0.26 0.075 31 11 20
024 9.7 34.8 0.62 0.218 100 0.39 0.112 50 14 25
*Permissible limits of the voltage range at which the unit will operate satisfactorily
LEGEND
FLA --- Fu l l L o a d A m ps
LRA --- L o c k e d R o t o r A m p s
MCA --- Minimum Circuit Amps
RLA ---RatedLoadAmps
38/40MVC, MVQ

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier High Wall Duct Free Split System 38MVC and is the answer not in the manual?

Carrier High Wall Duct Free Split System 38MVC Specifications

General IconGeneral
BrandCarrier
ModelHigh Wall Duct Free Split System 38MVC
CategoryAir Conditioner
LanguageEnglish

Related product manuals