ELECTRICAL DATA
UNIT
S I Z E ---
VOLTAGE,
SERIES
V/PH
OPER VOLTS* COMPR FAN
MCA
MIN
WIRE
SIZE{
MIN
WIRE
SIZE{
MAX
LENGTH
ft (m)}
MAX
LENGTH
ft (m)}
MAX
FUSE**
or CKT
BRK
AMPS
MAX MIN LRA RLA FLA 60°C 75°C 60°C 75°C
24--- 30
208/230/1 253 197
52.0 12.7 0.6 16.5 14 14 48 (14.6) 45 (13.7) 25
36--- 30 82.0 16.7 0.9 21.8 12 12 57 (17.4) 55 (16.8) 35
48--- 30 96.0 26.9 1.3 34.9 8 10 89 (27.1) 54 (16.5) 50
60--- 30 118.0 23.0 1.4 30.2 8 10 103 (31.4) 63 (19.2) 50
* Permissible limits of the voltage range at which the unit will operate satisfactorily
{ If wire is applied at ambient greater than 30_C , c o n s u l t t a bl e 3 1 0 --- 1 6 o f t h e N E C ( N F PA 7 0 ) . T h e a m p a c it y o f n o n --- m e t a l l i c --- sh e a t h e d c a bl e ( N M ) ,
trade n ame ROMEX, shall be that of 60_C conditions, per the NEC (NFPA 70) Article 336 ---26. If other than uncoated (no---plated), 60 or 75_C
insulation, copper wire (solid wire for 10 A WG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (NFPA 70).
} Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%.
* * T i m e --- D e l a y f u s e .
FLA --- Fu l l L o a d A m p s
LRA --- L o c k e d R o to r A m p s
M C A --- Minimum Circuit Amps
RLA --- RatedLoadAmps
NOTE: Control circuit is 24---V on all units and requires external power source. Copper wire must be used from service disconnect to unit.
All motors/compressors contain internal overload protection.
Complies with 2010 requirements of ASHRAE Standards 90.1
SOUND POWER LEVEL (dBA)
Unit Size
--- V o l t a g e ,
Series
Standard Rating dBA
TYPICAL OCTAVE BAND SPECTRUM (dBA, without tone adjustment)
125 250 500 1000 2000 4000 8000
24
6 8 --- H i g h S t a g e 53.0 55.0 59.0 62.0 59.5 58.0 53.5
6 7 --- L o w S t a g e 52.0 56.0 59.5 60.5 61.0 58.0 49.0
36
7 1 --- H i g h S t a g e 53.0 59.0 62.0 64.0 60.0 58.5 50.5
7 1 --- L o w S t a g e 53.4 60.0 63.0 65.5 61.5 58.0 49.0
48
7 0 --- H i g h S t a g e 54.5 61.5 63.5 64.5 61.0 57.5 52.0
7 0 --- L o w S t a g e 55.5 61.0 64.5 64.0 61.0 57.0 49.5
60
7 2 --- H i g h S t a g e 53.5 62.0 66.0 66.5 61.5 58.0 52.0
7 2 --- L o w S t a g e 54.0 62.0 66.5 67.0 60.5 57.5 51.0
NOTE: Tested in compliance with ARI 270 ---2008 but not listed with AHRI.
CHARGING SUBCOOLING (TXV--TYPE EXPANSION DEVICE)
UNIT SIZE--- VOL TAGE, SERIES REQUIRED SUBCOOLING _F(_C)
24--- 30 9.0 (5.0)
36--- 30 12.0 (6.7)
48--- 30 12.0 (6.7)
60--- 30 11.0 (6.1)