25TPB7: Installation Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
9
Sequence of Operation
NOTE: Defrost control board is equipped with 5 minute lockout timer
that is initiated upon any interruption of power. 
Turn on power to indoor and outdoor units. Transformer is energized. 
These models utilize a  2-stage  indoor thermostat.  With  a  call for first
(low)  stage  cooling  or  heating,  the  outdoor  fan  and  low-stage
compressor are energized.  If low-stage cannot satisfy cooling or heating
demand, high-stage is energized by the second (high) stage of the indoor
thermostat.    After  the  second  stage  is  satisfied,  the  unit  returns  to
low-stage  operation  until  second  stage  is  required  again.   When  both,
first and  second  stage  cooling  or  heating  are satisfied,  the  compressor
will shut off.
Cooling
With  first  stage  cooling,   Y1  and  O  are  powered  on;  and  with  second
stage  cooling,   Y2,  Y1  and  O  are  powered  on.    The  O  energizes  the
reversing valve, switching it to  cooling position.  The Y1 signal sends
low  voltage  through  the  safeties  and  energizes  the  T1  terminal  on  the
circuit board.  If the compressor has been off for 5 minutes, or power has
not  been  cycled  for  5  minutes,  the  OF2  relay  and  T2  terminal  will
energize.  This will close  the contactor  and start the outdoor fan motor
and compressor.  When the cycle is complete, Y1 is turned off, stopping
the  compressor  and  outdoor  fan.    The  5  minute  time  guard  begins
counting.  Compressor will not come on until this delay expires.  In the
event  of  a  power  interruption,  the  time  guard  will  not  allow  another
cycle for 5 minutes.
Heating
With first  stage  heating, Y1 is powered on; with second  stage  heating,
Y2 and Y1  are powered on.  The Y1 signal sends  low  voltage  through
the safeties  and  energizes  the T1  terminal on  the circuit board.   If  the
compressor has been off for 5 minutes or power has not been cycled for
5 minutes, the OF2 relay and T2 terminal will energize.  This will close
the contactor and start the outdoor fan motor and compressor.
When the  cycle is complete, Y1 is turned off, stopping the  compressor
and outdoor fan.  The 5 minute time guard begins counting.  Compressor
will  not  come  on  until  this  delay  expires.    In  the  event  of  a  power
interruption, the time guard will not allow another cycle for 5 minutes.
Compressor Operation
The  basic  scroll  design  has  been  modified  with  the  addition  of  an
internal  unloading  mechanism  that  opens  a  by-pass  port  in  the  first
compression pocket, effectively reducing the displacement of the scroll.
The opening and closing of the by-pass port is controlled by an internal
electrically operated solenoid.  The modulated scroll uses a single step of
unloading to go from full capacity to approximately 67% capacity.
A single speed, high efficiency motor continues to run while the scroll
modulates between  the two capacity steps.  Modulation is  achieved  by
venting a portion of the gas in the first suction pocket back to  the low
side of the  compressor, thereby reducing  the effective displacement of
the compressor.
Full  capacity  is  achieved  by  blocking  these  vents,  thus  increasing  the
displacement to 100%. A DC solenoid in the compressor controlled by a
rectified 24 volt AC signal in the external solenoid plug moves the slider
ring that covers and uncovers these vents.
The  vent  covers  are  arranged  in  such  a  manner  that  the  compressor
operates  at  approximately  67%  capacity  when  the  solenoid  is  not
energized  and  100%  capacity  when  the  solenoid  is  energized.    The
loading and unloading of the two step scroll is done ”on the fly” without
shutting off the motor between steps.
NOTE:  67%  compressor  capacity  translates  to  approximately  75%
cooling or heating capacity at the indoor coil.
The  compressor will  always  start unloaded  and  stay unloaded for  five
seconds even when the thermostat is calling for high stage capacity.
Quiet Shift-2
Quiet  shift-  2  is  a  field  selectable  defrost  mode  (factory  set  to  OFF),
which will reduce the occasional noise that could be heard at the start of
defrost cycle and restarting of heating cycle. It is selected by placing DIP
switch  3  on  defrost  board  in  the  ON  position.    When  Quiet  Shift-  2
switch is  placed in ON position, and  defrost is  initiated, the following
sequence of operation will occur: The compressor will be de- energized
for approximately 1 minute, then the reversing valve will be energized.
A few seconds later, the compressor will be re- energized and the normal
defrost cycle starts.
Once  defrost  termination  conditions  have  been  met,  the  following
sequence  will  occur:  The  compressor  will  be  de-  energized  for
approximately 1 minute, then the reversing valve will be de- energized.
A few seconds later, the compressor will be re- energized and the normal
heating cycle starts.
Defrost
The  defrost  control  is  a  time/temperature  control  which  has  field
selectable  settings  of  30,  60,  90,  or  120  minutes,  factory  set  to  60
minutes. These settings represent  the initial  time  period that must pass
after  closure  of  the  defrost  thermostat  before  the  defrost  sequence
begins, after which the defrost period varies with defrost length.  If Quiet
Shift  2  is  enabled,  the  variable  defrost  intervals  will  be  disabled  to
provide options where using a specific setting is desired.  In this case the
30, 60, 90, or 120 minutes setting will not change unless the dipswitch is
changed and power is cycled.
The  defrost  thermostat  senses  coil  temperature throughout the  heating
cycle. When the  coil temperature reaches  the defrost thermostat setting
of  approximately  32°F  (0°C),  it  will  close,  which  energizes  the  DFT
terminal  and  begins  the  defrost  timing  sequence.  When  the  DFT  has
been  energized for  the selected  time,  the defrost  cycle  begins. Defrost
cycle is terminated when defrost thermostat opens, or automatically after
10 minutes.
Defrost Speedup
To initiate a forced defrost, speedup pins (J1) must be shorted with a flat
head  screwdriver  for  5  seconds  and  RELEASED.  If  the  defrost
thermostat is open, a short defrost cycle will be observed (actual length
depends on Quiet Shift- 2 switch position). When Quiet Shift- 2 is off,
only a short 30 second defrost cycle is observed. With Quiet Shift- 2 ON,
the speedup sequence is approximately 3 minutes; 1 minute compressor
off period followed by 30 seconds of defrost with compressor operation.
When  returning  to  heating  mode,  the  compressor  will  turn  off  for  an
additional 1 minute.
If the defrost thermostat is closed, a complete defrost cycle is initiated. If
the Quiet Shift- 2 switch is turned on, the compressor will be turned off
for two 1 minute intervals as explained previously.
A05378
Fig. 11 – Defrost Control