25TPB7: Installation Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
10
Check Charge
NOTE: CHARGE IN HIGH STAGE ONLY.
Factory charge amount and desired subcooling are shown on unit rating
plate.  Charging  method  is  shown  on  information  plate  inside  unit. To
properly  check  or  adjust  charge,  conditions  must  be  favorable  for
subcooling  charging.  Favorable  conditions  exist  when  the  outdoor
temperature  is  between  70°F  and  100°F  (21.1°C  and  37.8°C), and  the
indoor  temperature  is  between  70°F  and  80°F  (21.1°C  and  26.7°C).
Follow the procedure below:
Unit  is  factory  charged  for  15ft    (4.6  m)  of  lineset. Adjust  charge  by
adding  or  removing  0.6  oz/ft    (.018  kg/m) of  3/8  liquid line  above  or
below 15ft (4.6 m) respectively.
For standard refrigerant line lengths (80 ft/24.4 m or less), allow system
to  operate  in  cooling  mode  at  least  15  minutes.  If  conditions  are
favorable, check system charge by subcooling method. If any adjustment
is  necessary,  adjust  charge  slowly and  allow  system  to  operate  for  15
minutes to stabilize before declaring a properly charged system. 
If  the  indoor  temperature  is  above  80°F  (26.7°C),  and  the  outdoor
temperature  is  in  the  favorable  range,  adjust  system  charge  by  weight
based on line length and allow the indoor  temperature to drop to 80°F
(26.7°C)  before  attempting  to  check  system  charge  by  subcooling
method as described above. 
If  the  indoor  temperature  is  below  70°F  (21.1°C),  or  the  outdoor
temperature is not in the favorable range, adjust charge for line set length
above  or  below  15ft  (4.6  m)  only.  Charge  level  should  then  be
appropriate  for  the  system  to achieve  rated  capacity. The charge level
could then be checked at another time when the both indoor and outdoor
temperatures are in a more favorable range.
NOTE: If line length is beyond 80 ft (24.4 m) or greater than 20 ft (6.1
m)  vertical  separation,    See  Long Line  Guideline  for  special  charging
requirements.
Heating Check Chart Procedure
To  check  system  operation  during  heating  cycle,  refer  to  the  Heating
Check  Chart  on  outdoor  unit.  This  chart  indicates  whether  a  correct
relationship  exists  between  system  operating  pressure  and  air
temperature  entering  indoor  and  outdoor  units.  If  pressure  and
temperature do not match on chart, system refrigerant charge may not be
correct. Do not use chart to adjust refrigerant charge. 
Verify units for proper switching between low & high 
stages 
Check  the  suction  pressures  at  the  service  valves.      Suction  pressure
should be reduced by 3-10% when switching from low to high capacity.  
Compressor current should increase 20-45% when  switching from low
to high stage.   The compressor solenoid when energized in high stage,
should measure 24vac at leads inside control box.  
When the compressor is operating in low stage the 24v DC compressor
solenoid coil is de-energized.  When the compressor is operating in high
stage, the 24v DC solenoid coil is energized.  The solenoid plug harness
that  is  connected  to  the  compressor  HAS  an  internal  rectifier  that
converts the 24v AC signal to 24v DC.  DO NOT INSTALL A PLUG
WITHOUT AN INTERNAL RECTIFIER.
Unloader Test Procedure
The  unloader  is the  compressor  internal  mechanism,  controlled  by  the
DC  solenoid,  that  modulates  between  high  and  low  stage.    If  it  is
suspected that the unloader is not working, the following methods may
be used to verify operation.
1. Operate the system and measure compressor amperage.  Cycle the
unloader  on  and  off  at  30  second  plus  intervals  at  the  thermostat
(from  low  to  high  stage  and  back  to  low  stage).    Wait 5  seconds
after  staging  to  high  before  taking  a  reading.    The  compressor
amperage should go up or down at least 20 percent.
2. If    the expected  result is  not  achieved,  remove  the  solenoid  plug
from the compressor and with the unit running and the thermostat
calling for high stage, test the voltage output at the plug with a DC
voltmeter.  The reading should be 24 volts DC.
3. If  the  correct  DC  voltage  is  at  the  control  circuit  molded  plug,
measure  the  compressor  unloader  coil  resistance.    The  resistance
should be approximately 1640  milliohms.  If the coil resistance is
infinite or is grounded, the compressor must be replaced.    
Final Checks
IMPORTANT: Before leaving job, be sure to do the following:
1. Ensure that all wiring is routed away from tubing and sheet metal
edges to prevent rub-through or wire pinching. 
2. Ensure  that  all  wiring  and  tubing  is  secure  in  unit  before  adding
panels and covers. Securely fasten all panels and covers. 
3. Tighten service valve stem caps to 1/12-turn past finger tight.
4. Leave Owner’s Manual with owner. Explain system operation and
periodic maintenance requirements outlined in manual. 
5. Fill out Dealer Installation Checklist and place in customer file.