Install Liquid Line Filter Drier Indoor
Refer to Fig. 6 and install filter drier as follows:
1. Braze 5 in. (127 mm) liquid tube to the indoor coil.
2. Wrap filter drier with damp cloth.
3. Braze filter drier to 5 in. (127 mm) long liquid tube from step 1. 
4. Connect and braze liquid refrigerant tube to the filter drier. 
A05227
Fig. 6 – Liquid Line Filter Drier
Refrigerant tubing and indoor coil are now ready for  leak testing. This
check should include all field and factory joints. 
Evacuate Refrigerant Tubing and Indoor Coil
Refrigerant  tubes  and  indoor  coil  should  be  evacuated  using  the
recommended deep vacuum method of 500 microns. The alternate triple
evacuation  method  may  be  used  (see  triple  evacuation  procedure  in
service manual).  Always break a vacuum with dry nitrogen.
Deep Vacuum Method
The deep vacuum method requires a vacuum pump capable of pulling a
vacuum  of  500  microns  and  a  vacuum  gage  capable  of  accurately
measuring  this  vacuum  depth.  The  deep  vacuum  method  is  the  most
positive way of assuring a system is free of air and liquid water. A tight
dry system will hold a vacuum of 1000 microns after approximately 7
minutes.  See Fig. 7.
A95424
Fig. 7 – Deep Vacuum Graph
Final Tubing Check
IMPORTANT: Check to  be certain factory tubing on both indoor and
outdoor  unit  has  not  shifted  during  shipment.  Ensure  tubes  are  not
rubbing  against  each  other  or  any  sheet  metal.  Pay  close  attention  to
feeder tubes, makings sure wire ties on feeder tubes are secure and tight.
Be  sure  field  wiring  complies  with  local  and  national  fire,  safety,  and
electrical  codes,  and  voltage  to  system  is  within  limits  shown  on  unit
rating  plate.  Contact  local  power  company  for  correction  of  improper
voltage. See unit rating plate for recommended circuit protection device. 
NOTE: Operation of unit on improper line voltage constitutes abuse and
could affect unit reliability. See unit rating plate. Do  not install unit in
system where voltage may fluctuate above or below permissible limits.
Make Electrical Connections
NOTE: Use copper wire only between disconnect switch and unit.
NOTE:  Install  branch  circuit  disconnect of  adequate  size  per  NEC  to
handle  unit  starting  current.  Locate  disconnect  within  sight  from  and
readily accessible from unit, per Section 440-14 of NEC.
Route Ground and Power Wires
Remove access panel to gain access to unit wiring. Extend wires from
disconnect  through  power  wiring  hole  provided  and  into  unit  control
box.
Connect Ground and Power Wires
Connect  ground  wire  to  ground  connection  in  control  box  for  safety.
Connect power wiring to contactor as shown in Fig. 8.
CAUTION
!
UNIT DAMAGE HAZARD
Failure  to  follow  this  caution  may  result  in  equipment  damage  or
improper operation.
1. Installation of  filter  drier  in liquid line is  required.
2. Filter drier must be wrapped in a heat-sinking material such as a
wet cloth while brazing.
CAUTION
!
UNIT DAMAGE HAZARD
Failure  to  follow  this  caution  may  result  in  equipment  damage  or
improper operation.
Never use the system compressor as a vacuum pump.
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Do  not  supply  power  to  unit  with  compressor  terminal  box  cover
removed.
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
The  unit  cabinet  must  have  an  uninterrupted  or  unbroken  ground  to
minimize personal injury if an electrical fault should occur. The ground
may  consist  of  electrical  wire  or  metal  conduit  when  installed  in
accordance with existing electrical codes. 
500
MINUTES
01234567
1000
1500
LEAK IN
SYSTEM
VACUUM TIGHT
TOO WET
TIGHT
DRY SYSTEM
2000
MICRONS
2500
3000
3500
4000
4500
5000