Option 34 -- Hybrid Heat Furnace Latch
This selection allows a Hybrid Heat system to finish a heating cycle using the
furnace.
On -- Once the furnace is on, it will finish the heating cycle with the furnace. If a
heat pump defrost occurs, the heating cycle will finish with the furnace.
OF -- The system will stage from furnace back to heat pump if heating demand
dictates, or 2 minutes after a defrost has ended.
Default is On.
Option 40 Humidify Fan
This selection controls whether humidification can only be done when a heating
demand is present. If the homeowner turns humidification OFF, this configuration
operates as if the selection was set to OFF.
OF -- The humidity output will only energize when there is a humidity demand and
the heating equipment is energized.
On -- The humidity output and the fan will energize anytime humidification is
needed during heating mode regardless of the state of the heating equipment.
Factory default is OF (Off)
Option 41 Variable Speed Blower
This selection allows the installer to select between a single speed or variable motor.
In a system with a two speed compressor (A2, h2, H2), if a dehumidification
demand exists and the compressor is energized for cool to dehumidify, cooling, or
both, and the system has a PSC blower (Option 41 = OFF), then both Y/Y2 and
Y1/W2 are energized.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier Performance TP-PRH-A and is the answer not in the manual?

Carrier Performance TP-PRH-A Specifications

General IconGeneral
BrandCarrier
ModelPerformance TP-PRH-A
CategoryThermostat
LanguageEnglish

Related product manuals