MODIFYING THE VALUE OF A PARAMETER
OPERATION PRESS BUTTON MENU LED ITEM NUMBER ITEM VALUE
2-DIGIT DISPLAY 4-DIGIT DISPLAY
Hold on the MENU button until the LED for SETPOINT lights.
Press one of the Arrow buttons until the two-digit display shows 1
(item number 1- cooling setpoint 2).
The value for setpoint 2 is displayed in the four-digit display (6.0°C in this
example).
Press the Enter button for more than 2 seconds to enable the value associated
with item 1 to be modified.
The Setpoint menu LED flashes indicating that modification mode is active.
Keep pressing the Down Arrow button until the value 5.7 is displayed in the four-
digit display. The Setpoint menu LED keeps flashing.
Press the Enter button again to validate the change. The new setpoint is 5.7°C.
The Setpoint menu LED stops flashing, indicating that modification mode no
longer applies.
4.3.4 - Expand display
Pressing the Enter button causes a 23 character text expansion to
be scrolled across the four-digit display. All user menus
provide an expansion of the current displayed parameters. If
the expansion is complete the four-digit display reverts to item
value. This function can be inhibited through the User
Configuration menu.