27
ACTIVE OPERATING TYPE PARAMETER STATUS CONTROL UNIT
TYPE STATUS
REMOTE MASTER UNIT START/STOP CCN GENERAL
START/STOP CONTROL SCHEDULE EMERGENCY ALARM
LOFF L-C L-SC rEM CCN MASt CHIL_S_S CONTACT TYPE MODE SHUTDOWN
- - - - - - - - - - Enable - - Off
------- - -. -. - Yes - Off
Active - - - - - - - - - - - Local Off
- - Active - - - - - - Unoccupied - - Local Off
- - - Active - - - Off - - - - Remote Off
- - - Active - - - - - Unoccupied - - Remote Off
- - - - Active - Disable - - - - - CCN Off
- - - - Active - - - - Unoccupied - - CCN Off
- - - - - Active - - Local Unoccupied - - Local Off
- - - - - Active - Off Remote - - - Remote Off
- - - - - Active - - Remote Unoccupied - - Remote Off
- - - - - Active Disable - CCN - - - CCN Off
- - - - - Active - - CCN Unoccupied - - CCN Off
- Active - - - - - - - - Disable No Local On
- - Active - - - - - - Occupied Disable No Local On
- - - Active - - - On - Occupied Dsable No Remote On
- - - - Active - Enable - - Occupied Disable No CCN On
- - - - - Active - - Local Occupied Disable No Local On
- - - - - Active - On Remote Occupied Disable No Remote On
- - - - - Active Enable - CCN Occupied Disable No CCN On
PARAMETER STATUS
ON/OFF CONTROL HEATING/COOLING OR HEAT RECLAIM REMOTE HEATING/COOLING HC_SEL or OPERATING MODE
STATUS TYPE SELECTION IN LOCAL MODE OR HEAT RECLAIM CONTACTS RECL_SEL
Off - - - - Cooling Normal
On Local Cooling - - Cooling Normal
On Local Heating - - Heating Heat reclaim
On Remote - Cooling mode - Cooling Normal
On Remote - Heating mode - Heating Heat reclaim
On CCN - - Cooling Cooling Normal
On CCN - - Heating Heating Heat reclaim

Related product manuals