EasyManua.ls Logo

Carrier PRO-DIALOG PLUS 30RW - Page 29

Carrier PRO-DIALOG PLUS 30RW
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
29
The following table summarises the possible selections
depending on the control types (local, remote or CCN) and the
following parameters:
- Setpoint select in local control: item #13 of the Infor-
mation menu permits selection of the active setpoint, if the
unit is in local operating type.
- Heating/cooling operating mode
- Control contacts: status of control contacts 5 and 6 (dual-
circuit units only). These contacts are only active if the
unit is in remote control operating type. See section 3.6.4.
- Control contact 3: status of control contact 3 (single-
circuit units only). See section 3.6.2.
- Contol contact 3 selection: this selection, only used for
single-circuit units, indicates if contact 3 is used for dual
setpoint control or for demand limit control (see User
Configuration menu).
- Schedule 2 status: schedule for setpoint selection. See
section 4.3.11.6.
HEATING/COOLING
OPERATING MODE
Cooling
Cooling
Cooling
Cooling
Heating
Heating
Heating
Heating
Heating
Heating
LOCAL
SETPOINT
SELECTION
sp 1
sp 2
Auto
Auto
sp 1
sp 2
sp 3
Auto
Auto
Auto
SCHEDULE 2
STATUS
-
-
Occupied
Unoccupied
-
-
-
Occupied
Unoccupied
Holiday
ACTIVE SETPOINT
Cooling setpoint 1
Cooling setpoint 2
Cooling setpoint 1
Cooling setpoint 2
Heating setpoint 1
Heating setpoint 2
Heating setpoint 3
Heating setpoint 1
Heating setpoint 2
Heating setpoint 3
LOCAL OPERATING MODE
PARAMETER STATUS
HEATING/COOLING
OPERATING MODE
Cooling
Cooling
Cooling
Cooling
Heating
Heating
Heating
Heating
Heating
CONTROL CONTACT 3
SELECTION
Setpoint
Setpoint
Demand limit
Demand limit
Setpoint
Setpoint
Demand limit
Demand limit
Demand limit
CONTROL CONTACT 3
Setpoint 1
Setpoint 2
-
-
Setpoint 1
Setpoint 2
-
-
-
SCHEDULE 2 STATUS
-
-
Occupied
Unoccupied
-
-
Occupied
Unoccupied
Holiday
ACTIVE SETPOINT
Cooling setpoint 1
Cooling setpoint 2
Cooling setpoint 1
Cooling setpoint 2
Heating setpoint 1
Heating setpoint 2
Heating setpoint 1
Heating setpoint 2
Heating setpoint 3
REMOTE OPERATING MODE - SINGLE-CIRCUIT UNITS
PARAMETER STATUS
HEATING/COOLING
OPERATING MODE
Cooling
Cooling
Heating
Heating
Heating
SCHEDULE 2
STATUS
Occupied
Unoccupied
Occupied
Unoccupied
Holiday
ACTIVE SETPOINT
Cooling setpoint 1
Cooling setpoint 2
Heating setpoint 1
Heating setpoint 2
Heating setpoint 3
CCN OPERATING MODE
PARAMETER STATUS
HEATING/COOLING
OPERATING MODE
Cooling
Cooling
Cooling
Cooling
Cooling
Heating
Heating
Heating
Heating
Heating
Heating
CONTROL
CONTACTS
sp 1
sp 2
sp 3
Auto
Auto
sp 1
sp 2
sp 3
Auto
Auto
Auto
SCHEDULE 2
STATUS
-
-
-
Occupied
Unoccupied
-
-
-
Occupied
Unoccupied
Holiday
ACTIVE SETPOINT
Cooling setpoint 1
Cooling setpoint 2
Cooling setpoint 2
Cooling setpoint 1
Cooling setpoint 2
Heating setpoint 1
Heating setpoint 2
Heating setpoint 3
Heating setpoint 1
Heating setpoint 2
Heating setpoint 3
REMOTE OPERATING MODE - DUAL-CIRCUIT UNITS
PARAMETER STATUS

Related product manuals