R4A4S, R4A5S: Installation Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
5
Air Conditioner Applied as Replacement Component
If  the  air  conditioner  is  installed  as  a  replacement  component  in  an
existing piston indoor system, the piston size in the indoor unit should be
changed to the size required for the air conditioner which can be found in
the indoor unit Product Data 
Units with Cooling Mode TXV
Units  installed  with  cooling  mode  TXV  require  charging  by  the
subcooling method.
1. Operate unit a minimum of 15 minutes before checking charge.
2. Measure liquid service valve pressure by attaching an accurate gage
to service port. 
3. Measure liquid line temperature by attaching an accurate thermistor
type or electronic thermometer to liquid line near outdoor coil. 
4. Refer to unit rating plate for required subcooling temperature. 
5. Refer to Table 2 - Rating Plate (required) Subcooling Temperature.
Find  the  point  where  required  subcooling  temperature  intersects
measured liquid service valve pressure. 
6. To obtain required subcooling temperature at a specific 
liquid  line  pressure,  add  refrigerant  if  liquid  line  temperature  is
higher than indicated or reclaim refrigerant if temperature is lower.
Allow a tolerance of ±3°F (±1.7°C).
Units with Indoor Piston
Units  installed  with  indoor  pistons  require  charging  by  the  superheat
method. 
The  following  procedure  is  valid  when  indoor  airflow  is  within  ±21
percent of its rated CFM. 
1. Operate unit a minimum of 15 minutes before checking charge. 
2. Measure suction pressure by attaching an accurate gage to suction
valve service port. 
3. Measure  suction  temperature  by  attaching  an  accurate  thermistor
type or electronic thermometer to suction line at service valve. 
4. Measure outdoor air dry-bulb temperature with thermometer. 
5. Measure  indoor  air  (entering  indoor  coil)  wet-bulb  temperature
with a sling psychrometer. 
6. Refer  to  Table 3  -  Superheat  Charging  - AC  Only.  Find  outdoor
temperature  and  evaporator  entering air  wet-bulb  temperature. At
this intersection, note superheat. Where a dash (--) appears on the
table,  do  not  attempt  to  charge  system  under  these  conditions  or
refrigerant slugging may occur. Charge must be weighted in, adding
or  removing  0.6  oz/ft  of  3/8  liquid  line  above  or  below  15  feet
(4.6m) respectively.
7. Refer  to  Table 4  -  Required  Suction-Line  Temperature.  Find
superheat temperature (from #6 above) and suction pressure. At this
intersection, note suction line temperature.
8. If  unit  has  a  higher  suction  line  temperature  than  charted
temperature, add refrigerant until charted temperature is reached. 
9. If  unit  has  a  lower  suction  line  temperature  than  charted
temperature,  reclaim  refrigerant  until  charted  temperature  is
reached. 
10. When adding refrigerant, charge in liquid form into suction service
port using a flow-restricting device. 
11. If  outdoor  air  temperature  or  pressure  at  suction  valve  changes,
charge to new suction line temperature indicated on chart. 
12. Optimum performance will be achieved when the operating charge
produces 10°F suction superheat at suction service valve with 95°F
(35°C)  outdoor  ambient  and  80°F  (27°C)  dry  bulb  (67°F / 19°C)
wet  bulb)  indoor  temperature  (DOE “A”  test  conditions)  at  rated
airflow.