R4A4S, R4A5S: Installation Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
7
Make Electrical Connections
Be  sure  field  wiring  complies  with local  and  national  fire,  safety,  and
electrical codes, and voltage  to  system  is  within  limits  shown  on unit
rating  plate.  Contact  local  power  company  for  correction  of  improper
voltage. See unit rating plate for recommended circuit protection device.
NOTE: Operation of unit on improper line voltage constitutes abuse and
could affect unit reliability. See unit rating plate. Do  not install unit in
system where voltage may fluctuate above or below permissible limits.
NOTE: Use copper wire only between disconnect switch and unit.
NOTE:  Install  branch  circuit  disconnect  of  adequate  size  per  NEC  to
handle unit starting current. Locate disconnect within sight and readily
accessible from unit, per Section 440-14 of NEC. Refer to Product Data
for breaker sizing.
Route Ground and Power Wires
Remove access panel  to gain access to unit wiring. Extend wires from
disconnect  through  power  wiring  hole  provided  and  into  unit  control
box.
Connect Ground and Power Wires
This appliance incorporates an earth connection for safety purposes only.
Connect  ground  wire  to  ground  connection  in  control  box  for  safety.
Connect power wiring to contactor as shown in Fig. 6.
A94025
Fig. 6 – Line Connections
Connect Control Wiring
Route 24-v control wires through control wiring  grommet and connect
leads to control wiring.  Refer  to thermostat Installation Instructions for
wiring specific unit combinations (see Fig. 7 ).
Use  No.  18  AWG  color-coded,  insulated  (35°C  minimum)  wire.  If
thermostat  is  located more  than  100 ft.  (30  m)  from unit,  as measured
along  the control  voltage wires,  use  No.  16 AWG color-coded wire  to
avoid excessive voltage drop.
All wiring must be NEC Class 2 and must be separated from incoming
power leads. 
Use furnace transformer, fan coil transformer, or accessory transformer
for control power, 24v/40va minimum.
NOTE: Use of available 24v accessories may exceed the minimum 40va
power  requirement.  Determine  total    transformer  loading  and  increase
the transformer capacity or split the load with an accessory transformer
as required.
A02326A/A97368
Fig. 7 – Generic Wiring Diagrams (See Thermostat Installation Instruction for specific unit combinations)
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Do  not  supply  power  to  unit  with  compressor  terminal  box  cover
removed. 
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
The  unit  cabinet  must  have  an  uninterrupted  or  unbroken  ground  to
minimize personal injury if an electrical fault should occur. The ground
may  consist  of  electrical  wire  or  metal  conduit  when  installed  in
accordance with existing electrical codes. 
24 VAC HOT
24 VAC COM
R
C
G
W/W1
Y/Y2
R
C
C
A/C
THERMOSTAT
Typical
FAN COIL
AIR
CONDITIONER
G
W2
HEAT STAGE 1
COOL STAGE 1
INDOOR FAN
24 VAC HOT
24 VAC COM
R
C
G
W/W1
Y/Y2
R
C
C
A/C
THERMOSTAT
Typical
FURNACE
AIR
CONDITIONER
Y
G
W
HEAT STAGE 1
COOL STAGE 1
INDOOR FAN