R4A4S, R4A5S: Installation Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
4
Install Liquid-Line Filter Drier Indoor
Refer to Fig. 3 and install filter drier as follows:
1. Braze 5-in. liquid tube to the indoor coil. 
2. Wrap filter drier with damp cloth. 
3. Braze filter drier to above 5-in. (127 mm) liquid  tube. Flow arrow
must point towards indoor coil.
4. Connect and braze liquid refrigerant tube to the filter drier.
A05178
Fig. 3 – Liquid Line Filter Drier
Evacuate Refrigerant Tubing and Indoor Coil
Refrigerant  tubes  and  indoor  coil  should  be  evacuated  using  the
recommended deep vacuum method of 500 microns. The alternate triple
evacuation  method  may  be  used  (see  triple  evacuation  procedure  in
service manual).  Always break a vacuum with dry nitrogen.
Deep Vacuum Method
The deep vacuum method requires a vacuum pump capable of pulling a
vacuum  of  500  microns  and  a  vacuum  gage  capable  of  accurately
measuring  this  vacuum  depth.  The  deep  vacuum  method  is  the  most
positive way of assuring a system is free of air and liquid water. A tight
dry system will hold a vacuum of 1000 microns after approximately 7
minutes. See Fig. 4
A95424
Fig. 4 – Deep Vacuum Graph
Mandatory Requirements
Pressure Proof Check 
1. Preform a pressure check of the unit with a nitrogen charge of about
200psi. 
2. The Nitrogen holding charge must NOT decrease in pressure for 1
hour,  as  indicated  by  the  test  gauge.  The  measuring  test  gauge
resolution not exceeding 5% of the holding charge. 
Leak Check 
This leak check requires a vacuum pump capable of pulling a vacuum of
at least 500 microns and a vacuum gage capable of accurately measuring
this vacuum depth. 
1. Vacuum unit to 500 microns. 
2. When isolating the unit from the pump, the pressure shall not rise
above 1500 microns in 10 minutes. 
Final Tubing Check
IMPORTANT: Check to  be certain factory tubing on both indoor and
outdoor  unit  has  not  shifted  during  shipment.  Ensure  tubes  are  not
rubbing  against  each  other  or  any  sheet  metal  or  wires.  Pay  close
attention  to  feeder  tubes,  making  sure  wire  ties  on  feeder  tubes  are
secure and tight.   
Installing with Indoor Piston
Outdoor Unit Connected to Factory Approved Indoor Unit
Check piston size shipped with indoor unit to see if it matches required
indoor  piston  size.    If  it  does  not  match,  replace  indoor  piston  with
correct piston size.  
The piston included with the FMA, FMC and FMU fan coils are unique
to  those  products  and  CANNOT  be  replaced  with  the  piston  shipped
with  outdoor  unit.  Refer  to  the AHRI  Directory  to  check  if  a  certain
combination can use a piston or requires an accessory TXV.
When changing indoor piston, use a back−up wrench. Hand tighten hex
nut,  then  tighten  with  wrench  1/2  turn.  Do  not  exceed  30  ft−lbs.  The
indoor  piston  contains  a  Teflon  ring  (or  seal)  which  is  used  to  seat
against the inside of distributor body, and must be installed properly to
ensure proper seating. See Fig. 5
A10342
Fig. 5 – Indoor (Cooling) Piston
CAUTION
!
UNIT DAMAGE HAZARD
Failure  to  follow  this  caution  may  result  in  equipment  damage  or
improper operation.
1. Installation of  filter  drier  in liquid line is  required.
2. Filter drier must be wrapped in a heat-sinking material such as a wet
cloth while brazing.
CAUTION
!
UNIT DAMAGE HAZARD
Failure  to  follow  this  caution  may  result  in  equipment  damage  or
improper operation.
Never use the system compressor as a vacuum pump.
WARNING
!
FIRE HAZARD
Failure to following this warning could result in personal injury, death
and/or property damage. 
DO  NOT  USE  FLAMES  OR  IGNITION  SOURCES  TO  LEAK
CHECK.