Operation & Service Manual
Carrier Transicold Europe 31/03/07 Viento - Installation/Rev- #50/54
6. When refrigerant cylinder weight (scale) indicates that the
correct charge has been added, close the manifold valves.
Refrigerant charge
Viento 200 0.85 Kg ± 5%
Viento 300 1 Kg ± 5%
Viento 350 1,1 Kg ± 5%
NOTE
It is possible that all liquid may not be pulled into
the circuit.
Complete the charge in vapour through the
compressor.
Installation Commissioning Refrigerant charge