62
g. Press (Down Arrow) twice, the following display
appears:
h. Press OK to highlight the number in the bracket and
then use the and (Up and Down Arrow) keys to
select the number provided in Tables 28-32. Press OK
again to set the selected value.
i. Press the Back key once, the following display
appears:
j. Press (Down Arrow) once, the following display
appears:
k. Press OK, the following display appears:
l. Press (Down Arrow) once, the following display
appears:
m. Press OK to highlight the number and then use the
and (Up and Down Arrow) keys to select the num-
ber provided in Tables 28-32. Press OK again to set
the selected value.
n. Press the Back key once, the following display
appears:
o. Press (Down Arrow) once, the following display
appears:
p. Press OK, the following display appears:
q. Press OK to highlight the number in the bracket then
use the and (Up and Down Arrow) keys to
select the number provided in Tables 28-32. Press OK
again to set the selected value.
7. Setting References:
a. Press the Menu key to move the (triangle icon) so
it is positioned over Main Menu. The display shows
the following:
b. Press (Down Arrow) three times, the following
display appears:
c. Press OK, the following display appears:
d. Press OK again, the following display appears:
NOTE: If the bottom row displays a number other than 0.000,
press OK and use the and (Up and Down Arrow) key to
select 0.000.
e. Press (Down Arrow) once, the following display
appears:
NOTE: If the bottom row displays a number other than 60.000,
press OK and use the
and (Up and Down Arrow) key to
select 60.000.
f. Press the Back key until the following display
appears:
g. Press (Down Arrow) once to move the highlight to
the bottom row and then press OK. The following dis-
play appears:
h. Press OK once to highlight the number in the bracket.
Press OK again; the highlight moves to the current
percent value.
Use the and (Up and Down Arrow) keys and the
table below to enter the required Preset Reference
values.
8. Setting the Ramp Time:
a. Press the Back key until the following display appears:
b. Press (Down Arrow) twice, the following display
appears:
c. Press OK, the following display appears:
d. Press OK again to highlight the bottom row and use the
and (Up and Down Arrow) keys to select 10.00s.
Press OK again to set the selected Ramp up Time.
1-73 Flying Start
[1] Enabled
1—6* Load Depen. Setting
1—7* Start Adjustments
1—7* Start Adjustments
1—8* Stop Adjustments
1-80 Function at Stop
[0] Coast
1-82 Min Speed for Functio…
1.0 Hz
1—7* Start Adjustments
1—8* Stop Adjustments
1—8* Stop Adjustments
1—9* Motor Temperature
1-90 Motor Thermal Prote…
[4] ETR trip 1
0—** Operation / Display
1—** Load and Motor
2—** Brakes
3—** Reference / Ramps
3—0* Reference Limits
3—1* References
3-02 Minimum Reference
0.000
3-03 Maximum Reference
60.000
3—0* Reference Limits
3—1* References
3-10 Preset Reference
[0]0.00%
[0]0.00% Stop
[1]LL.LL%
Low Speed (see Tables 28-32, column
labeled “Preset References 3-10[1]” for
the proper % for each unit)
[2]MM.MM%
Medium Speed (see Tables 28-32, col-
umn labeled “Preset References 3-10[2]”
for the proper % for each unit)
[3]100% Override (High Speed)
[4]100%
High Speed (100% or close to 100% to
achieve the required CFM at high speed)
[5]0.00% Stop
[6]0.00% Stop
[7]0.00% Stop
3—0* Reference Limits
3—1* References
3—1* References
3—4* Ramp 1
3-41 Ramp 1 Ramp up Time
3.00s