63
e. Press (Down Arrow) once, the following display
appears:
f. Press OK again to highlight the bottom row and use the
and (Up and Down Arrow) keys to select 10.00s.
Press OK again to set the selected Ramp Down Time.
9. Setting Limits:
a. Press the Back key until the following display appears:
b. Press (Down Arrow) once, the following display
appears:
c. Press OK, the following display appears:
d. Press OK again, the following display appears:
e. Press (Down Arrow) once, the following display
appears:
f. Press (Down Arrow) again, the following display
appears:
NOTE: Press OK to highlight the Hz value and then use the
and (Up and Down Arrow) keys to enter the required values.
g. Press (Down Arrow) once, the following display
appears:
NOTE: Press OK to highlight the % value and then use the
and (Up and Down Arrow) keys to enter the required value.
See Tables 28-32 for proper selection of the value for this parame-
ter, then press OK to set the selected value.
h. Press (Down Arrow) once, the following display
appears:
NOTE: Press OK to highlight the Hz value and then use the
and (Up and Down Arrow) keys to enter the required values.
10. Setting Digital Inputs:
a. Press the Back key until the following display appears:
b. Press (Down Arrow) once, the following display
appears:
c. Press OK, the following display appears:
d. Press (Down Arrow) once to move the highlight to
the bottom row and then press OK. The following dis-
play appears:
e. Press (Down Arrow) again. The following display
appears:
f. Press (Down Arrow) again. The following display
appears:
g. Press (Down Arrow) again. The following display
appears:
NOTE: By pressing
OK, the number in the bracket can be
changed until the desired number appears. Press OK again to set
the selected value.
11. Setting Analog Inputs:
a. Press the Back key until the following display appears:
b. Press (Down Arrow) until the following display
appears:
c. Press OK, the following display appears:
d. Press (Down Arrow) once to move the highlight to
the bottom row and then press OK. The following dis-
play appears:
e. Press (Down Arrow) once to move the highlight to
the bottom row and then press OK. The following dis-
play appears:
f. Press (Down Arrow) once to move the highlight to
the bottom row and then press OK. The following dis-
play appears:
g. Press (Down Arrow) once to move the highlight to
the bottom row and then press OK. The following dis-
play appears:
3-42 Ramp 1 Ramp Down Time
3.00s
2—** Brakes
3—** Reference / Ramps
3—** Reference / Ramps
4—** Limits / Warnings
4—1* Motor Limits
4—4* Adj. Warning 2
4-10 Motor Speed Direction
[2] Both Directions
4-12 Motor Speed Low Limi…
0.0Hz
4-14 Motor Speed High Limi…
65.0Hz
4-18 Current Limit
110%
4-19 Max Output Frequency
65.0Hz
3—** Reference / Ramps
4—** Limits / Warnings
4—** Limits / Warnings
5—** Digital In/Out
5—0* Digital I/O mode
5—1* Digital Inputs
5-10 Terminal 18 Digital In…
[8] Start
5-11 Terminal 19 Digital In…
[16] Preset ref bit 0
5-12 Terminal 27 Digital In…
[17] Preset ref bit 1
5-13 Terminal 29 Digital In…
[18] Preset ref bit 2
4—** Limits / Warnings
5—** Digital In/Out
5—** Digital In/Out
6—** Analog In/Out
6—** Analog In/Out
6—1* Analog Input 53
6-10 Terminal 53 Low Voltage
2V
6-11 Terminal 53 High Voltage
[10V]
6-14 Set Min Reference
[0 Hz]
6-15 Set Max Reference
[60 Hz]