29
The  thru-base  gas  connector  has  male and  female  threads.  The
male  threads protrude above the  basepan of the unit; the female
threads protrude below the basepan. 
Check tightness of connector lock nuts before connecting gas pip-
ing.
Install a 
3
/
4
-in. NPT street elbow (field-supplied) on the thru-base
gas fitting. Attach a 
3
/
4
-in. pipe nipple with minimum length of 
16-in. (406 mm) (field-supplied) to the street elbow and extend it
through the access panel at the gas support bracket (see Fig. 39).
Fig. 39 — Gas Line Piping (Size 16)
ALL UNITS
Other  hardware  required  to  complete  the  installation of the  gas
supply line will include a manual shutoff valve, a sediment trap
(drip leg),  and  a  ground-joint  union. A  pressure  regulator  valve
may  also  be  required  (to  convert  gas  pressure  from  pounds  to
inches  of  pressure).  The  manual  shutoff  valve  must  be  located
within 6 ft (1.83 m) of the unit. The union, located in the final leg
entering the unit, must be located at least 9-in. (230 mm) away
from the access panel to permit the panel to be removed for ser-
vice. If a regulator valve is installed, it must be located a minimum
of 4 ft (1220 mm) away from the unit’s flue outlet. Some munici-
pal  codes  require  that  the  manual  shutoff  valve  be  located  up-
stream of the sediment trap. See Fig. 40 and 41 for typical piping
arrangements for gas piping that has been routed through the side-
wall of the curb. See Fig. 42 for typical piping arrangement when
thru-base is used. Ensure that all piping does not block access to
the unit’s main control box or limit the required working space in
front of the control box.
Fig. 40 — Gas Piping with Thru-Curb Accessory
Fig. 41 — Gas Piping with Thru-Curb Accessory 
(Alternate Layout)
Fig. 42 — Gas Piping Thru-Base Connections
When installing the gas supply line, observe local codes pertaining
to  gas  pipe  installations.  Refer  to  the  NFPA  54/ANSI  Z223.1
NFGC latest  edition  (in Canada, CAN/CSA B149.1). In the ab-
sence  of local building  codes,  adhere to the following pertinent
recommendations:
1. Avoid low spots in long runs of pipe. Grade all pipe 
1
/
4
-in.
in every 15 ft (7 mm in every 5 m) to prevent traps. Grade
all horizontal runs downward to risers. Use risers to con-
nect to heating section and to meter.
2. Protect all segments of piping system against physical and
thermal  damage.  Support  all  piping  with  appropriate
straps, hangers, etc. Use a minimum of one hanger every
6 ft (1.8 m). For pipe sizes larger than 
1
/
2
-in., follow rec-
ommendations of national codes.
3. Apply joint compound (pipe dope) sparingly  and only to
male threads of joint when making pipe connections. Use
only pipe dope that is resistant to action of liquefied petro-
leum gases as specified by local and/or national codes. If
using PTFE (Teflon
1
) tape, ensure the material is Double
Density  type  and  is  labeled  for  use  on  gas  lines. Apply
tape per manufacturer’s instructions.
3
/
4
-in. NPT
STREET
ELBOW
THRU-BASE
GAS FITTING
GAS
SUPPORT
BRACKET
9” (229 mm) MIN.
UNION 
SHUT OFF
VALVE
DRIP
LEG
THRU-CURB ADAPTER
UNIT BASE RAIL
1. Teflon is a registered trademark of DuPont Corporation.
DRIP
LEG
SHUT OFF
VALVE
UNION
THRU-CURB ADAPTER
BURNER
ACCESS
PANEL
9” (229 mm) MIN. 
UNIT BASE RAIL