EasyManua.ls Logo

Carrier WeatherMaker 50TC07 Series - Economi$Er X (Factory-Installed Option); Product Description; System Components; Specifications

Carrier WeatherMaker 50TC07 Series
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
55
Fig. 90 — Typical Rooftop Unit with Humidi-MiZer
®
Adaptive Dehumidification System with
Edge
®
Pro Thermidistat Device
EconoMi$er
®
X (Factory-Installed Option)
PRODUCT DESCRIPTION
The EconoMi$er X system is an expandable economizer con-
trol system, which includes a W7220 economizer module (con-
troller) with an LCD and keypad (see Fig. 91). The W7220 can
be configured with optional sensors.
Fig. 91 — W7220 Economizer Module
The W7220 economizer module can be used as a stand-alone
economizer module wired directly to a commercial set-back
space thermostat and sensors to provide outside air dry-bulb
economizer control.
The W7220 economizer module can be connected to optional
sensors for single or differential enthalpy control. The W7220
economizer module provides power and communications for
the sensors.
The W7220 economizer module automatically detects sensors
by polling to determine which sensors are present. If a sensor
loses communications after it has been detected, the W7220
economizer controller indicates a device fail error on its LCD.
SYSTEM COMPONENTS
The EconoMi$er X system includes an economizer module,
20k mixed air sensor, damper actuator, and either a 20k out-
door air temperature sensor or S-Bus enthalpy sensors.
Economizer Module
The module is the core of the EconoMi$er X system. The mod-
ule is mounted in the unit’s control box, and includes the user
interface for the system. The W7220 economizer module pro-
vides the basic inputs and outputs to provide simple economiz-
er control. When used with the optional sensors, the economiz-
er module provides more advanced economizer functionality.
S-Bus Enthalpy Control Sensors
The sensor is a combination temperature and humidity sensor
which is powered by and communicates on the S-Bus. Up to three
sensors may be configured with the W7220 economizer module.
CO
2
Sensor (optional)
The sensor can be added for Demand Controlled Ventilation
(DCV).
SPECIFICATIONS
W7220 Economizer Module
The module is designed for use with 2 to 10 vdc or bus com-
municating actuator. The module includes terminals for CO
2
sensor, Mixed Air sensor, and an Outdoor Dry Bulb sensor. En-
thalpy and other options are available with bus sensors.
User Interface
Provides status for normal operation, setup parameters, check-
out tests, and alarm and error conditions with a 2-line 16 char-
acter LCD display and four button keypad.
Electrical
Rated Voltage — 20 to 30 vac RMS, 50/60 Hz
Transformer — 100 va maximum system input
Nominal Power Consumption (at 24 vac, 60 Hz) — 11.5 VA
without sensors or actuators
Rc
Rh
W1
G
Y2
C
O/W2/B
Y1
OAT
RR
S
S
RTN
HUM
D1
D2
V+
Vg
X
*
C
G
W2
W1
Y2
Y1
R
Edge Programable Thermostat
Unit CTB
THERMOSTAT
*Connection not required.
Humidi-MiZer™ FIOP

Table of Contents

Related product manuals