EasyManua.ls Logo

Carrier WeatherMaker 50TC07 Series - Belt Tension Method; Pre-Start and Start-Up; Troubleshooting the Ultratech Compressor; Modulation Control Input Specifications

Carrier WeatherMaker 50TC07 Series
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
82
Fig. 111 — V-Belt Force Label
BELT TENSION METHOD
Requires belt tension gage that measures tension in belt in units of
lbs force.
Fig. 112 — Belt Drive Motor Mounting
Pre-Start and Start-Up
This completes the mechanical installation of the unit. Refer to
the unit’s Service Manual for detailed Pre-Start and Start-Up
instructions. Download the latest versions from HVAC Part-
ners (www.hvacpartners.com).
Troubleshooting the UltraTech™ Compressor
The UltraTech
1
compressors molded plug should be used at all
times. The maximum power is 5A.
MODULATION CONTROL INPUT SPECIFICATIONS
The compressor will modulate from part load to full load when
the voltage supplied to the molded plug is 18 to 28vdc or 18 to
28 vac rectified to vdc. The compressor will modulate from
full load to part load when the current in the circuit drops be-
low 0.9 MA. See Table 19 and Fig. 113 for details.
Table 1
Table 2
BELT
CROSS
SECTION
SMALLEST
SHEAVE
DIAMETER
BELT DEFLECTION FORCE (LBS)
UNNOTCHED
BELTS
NOTCHED BELTS
USED NEW USED NEW
A, AX
3.0-3.6 3.7 5.5 4.1 6.1
3.8-4.8 4.5 6.8 5.0 7.4
5.0-7.0 5.4 8.0 5.7 8.4
B, BX
3.4-4.2 4.9 7.2
4.4-5.6 5.3 7.9 7.1 10.5
5.8-8.6 6.3 9.4 8.5 12.6
BELT CONDITION TENSION FORCE IN BELT (LBS)
New 100
Used 80
1. UltraTech™ is a trademark of Emerson Climate Technologies, Inc.
BLOWER PULLEY
V-BELT
MOTOR
PULLEY
MOTOR
MOTOR MOUNTING
PLATE
MOUNTING
BOLTS (4)
Table 19 — Troubleshooting UltraTech Compressor
STAGE CAPACITY METERING
LIQUID LINE
SOLENOID
COMPRESSOR
UNLOADER
FOR ULTRATECH
COMPRESSOR
TROUBLESHOOTING
(COMPRESSOR CURRENT)
FOR LIQUID LINE SOLENOID
VALVE TROUBLESHOOTING
(TOP EVAPORATOR COIL
TEMPERATURE)
Y1
Part Load
(66%)
TXV
Closed (De-
energized)
De-energized Approx. 80% or less
Top section of the evaporator
coil will not be cold (U-bend
tubes)
Y1+Y2
Full Load
(100%)
TXV+Fixed Open (Energized) Energized 100%
Top section of the evaporator
coil will be cold (U-bend tubes)

Table of Contents

Related product manuals