5. The unit pauses and then displays IN PROGRESS.
6. When the test is complete, DONE appears.
7. When all desired parameters have been tested, press the
(Menu Up) button to end the test.
The Checkout tests can all be performed at the time of installa-
tion or at any time during the operation of the system as a test
that the system is operable.
TROUBLESHOOTING
Alarms
The economizer module provides alarm messages that display
on the 2-line LCD.
NOTE: Upon power up, the module waits 60 minutes before
checking for alarms. This allows time for all the configured devic-
es (e.g. sensors, actuator) to become operational. The exception is
the SAT sensor which will alarm immediately.
If one or more alarms are present and there has been no keypad
activity for at least 5 minutes, the Alarms menu displays and
cycles through the active alarms.
You can also navigate to the Alarms menu at any time.
Clearing Alarms
Once the alarm has been identified and the cause has been re-
moved (e.g. replaced faulty sensor) the alarm can be cleared
from the display.
To clear an alarm, perform the following:
1. Navigate to the desired alarm.
2. Press the (Enter) button.
3. ERASE? displays.
4. Press the (Enter) button.
5. ALARM ERASED displays.
6. Press the (Menu up/Exit) button to complete the
action and return to the previous menu.
NOTE: If the alarm still exists after clearing it, it is redisplayed
within 5 seconds.
PremierLinkā„¢ Controller (Factory Option)
For details on operating 50TC**07-16 units equipped with the
factory-installed PremierLink controller option, refer to the
PREMIERLINK Retrofit Rooftop Controller Version 3.x In-
stallation, Start-up and Configuration Instructions.
See Fig. 97-100 for wiring diagrams.
RTU Open Controller (Factory-Installed Option)
For details on operating 50TC**07-16 units equipped with the
factory-installed RTU Open Controller option, refer to the Fac-
tory-Installed Option RTU Open Multi-Protocol Controller
Controls, Start-Up, Operation, and Troubleshooting manual.
See Fig. 101-107 for wiring diagrams.
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage.
Be sure to allow enough time for compressor start-up and
shutdown between checkout tests so that you do not short-
cycle the compressors.