Electrical data
* Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.
† Permissible limits of the voltage range at which the unit will operate satisfactorily.
‡ Time-delay type is recommended.
UNIT SIZE 040-12 060-08 060-12 080-14 080-16 100-12 100-16 100-20 120-16 120-20 135-20
UNIT VOLTS—HERTZ—PHASE 115—60—1
MINIMUM WIRE SIZE 14 14 14 14 14 14 14 12 14 12 12
MAXIMUM WIRE LENGTH (Ft)* 32 45 34 31 27 35 28 32 28 31 33
MAXIMUM UNIT AMPS 11.4 8.2 10.6 11.7 13.4 10.5 13.2 17.7 13.2 18.2 17.4
OPERATING VOLTAGE RANGE (Min—Max)† 104—127
MAX FUSE SIZE OR CKT BKR (Amps)‡ 15 15 15 15 15 15 15 20 15 20 20
TRANSFORMER (24v) 40va
EXTERNAL CONTROL POWER AVAILABLE Heating 19va
Cooling 35va
AIR CONDITIONING BLOWER RELAY Standard