24
WEIGHTS & DIMENSIONS (cont.)
C10465
Fig. 6 -- Dimensions 50HCQ 07--08
C
B
A
D
C10577
Fig. 7 -- Service Clearance
LOC DIMENSION CONDITION
A
48--- in. (1219 mm) Unit disconnect is mounted on panel
18--- in. (457 mm) No disconnect, convenience outlet option
18--- in. (457 mm) Recommended service clearance
12--- in. (305 mm) Minimum clearance
B
42--- in. (1067 mm) Surface behind servicer is grounded (e.g., metal, masonry wall)
36--- in. (914 mm) Surface behind servicer is electrically non--- conductive (e.g., wood, fiberglass)
Special Check for sources of flue products within 10--- ft of unit fresh air intake hood
C
36--- in. (914 mm) Side condensate drain is used
18--- in. (457 mm) Minimum clearance
D
42--- in. (1067 mm) Surface behind servicer is grounded (e.g., metal, masonry wall, another unit)
36--- in. (914 mm) Surface behind servicer is electrically non--- conductive (e.g., wood, fiberglass)
50HCQ